Free Shipping
Orders $75 & Up
-
30-day Money Back
Guarantee*
-
100% Secure Online Shopping
SSL - Verified Merchant
C&D Technologies UPS12-350MR Battery
C&D Technologies UPS12-350MR Battery
C&D Dynasty UPS12-350MR Battery - 12V 93.2 Ah High Rate Max AGM
Warranty
Same Width as the 300MR, Longer Case
- Absorbent glass mat, recombination up to 99% - efficient gas recombination and freedom from electrolyte maintenance over the life of the string.
- Patented flame-arresting vents - one UL-recognized valve in each of the six cells, on a UL94-V2 flame retardant case and cover.
- Top terminal, 1/4-20 UNC at 110 in-lbs - 12.4 N-m against 4,200 amps short-circuit current and a 0.003 ohm reference impedance.
- Standards on the sheet - UL1778, UL 924, UL 1989, UL 94 V-2, BS6290-4 and IEC-896-2, on a UL-recognized component.
- Any mounting orientation - C&D recommends upright, side or end, with half an inch between cases for convection.
Technical Specifications
| C&D UPS12-350MR Specifications | |
|---|---|
| Part Number | UPS12-350MR (also searched as UPS12 350MR, UPS12350MR; sold under the C&D Dynasty brand) |
| Series | UPS High Rate Max (MR), retired by C&D, replaced by UPS12-355PLP |
| Battery Type | AGM, valve regulated lead acid (VRLA), high rate |
| Nominal Voltage | 12V (6 cells per unit) |
| Nominal Capacity | 93.2 Ah at the 20-hour rate to 1.75 VPC at 25°C (77°F) |
| Watts Per Cell | 350 W per cell at the 15-minute rate to 1.67 VPC at 77°F |
| Constant Power to 1.75 VPC | 534 W/cell at 5 min, 410 at 10 min, 327 at 15 min, 272 at 20 min, 205 at 30 min, 119 at 60 min, 84.3 at 90 min |
| Constant Power to 1.67 VPC | 619 W/cell at 5 min, 440 at 10 min, 350 at 15 min, 289 at 20 min, 216 at 30 min, 123 at 60 min, 85.9 at 90 min |
| Terminal Type | Top terminal, threaded insert, 1/4-20 UNC bolt |
| Terminal Torque | 110 in-lbs (12.4 N-m) |
| Length | 12.04 inches (305.8 mm) |
| Width | 6.83 inches (173.4 mm) |
| Height | 7.94 inches to case top (201.6 mm) |
| Total Height | 8.06 inches over terminals (204.8 mm) |
| Weight | 67.4 lbs (30.5 kg) |
| Short Circuit Current | 4,200 A at 0.1 second |
| Impedance | 0.003 ohms at 60 Hz (reference figure; C&D recommends individual baselines) |
| Maximum Charging Current | C20/5 at the 20-hour rate, which is 18.6 A for this block |
| Operating Temperature | Discharge -40°F (-40°C) to +160°F (+71°C); charge -10°F (-23°C) to +140°F (+60°C) |
| Design Life | 10 year design life at 25°C (C&D) |
| Warranty | 3 years at 25°C (77°F) (C&D Form 41-9027, UPS High Rate Max series) |
| Minimum Order | 4 units |
Where This Battery Is Used
- Colocation and hosting halls - mid-size UPS cabinets stepping up from a 300MR string without changing terminal hardware.
- Testing laboratories - instrument and environmental-chamber power on a maintained float charge.
- Industrial process control facilities - controlled shutdown on lines that have to be brought down in sequence.
Ordering and Freight
Frequently Asked Questions
Will a UPS12-350MR drop into a tray cut for the UPS12-300MR?
In width and height, yes. The 350MR is 6.83 inches wide and 8.06 inches over the terminals against the 300MR's 6.83 and 8.01, a five-hundredth of an inch apart. The length is where it changes: 12.04 inches against 10.27, so each block needs 1.77 inches more run on the shelf, and a tier of ten needs nearly eighteen. Measure the tier before the order, not after delivery.
What is the maximum charging current for a UPS12-350MR?
C&D sets the recommended limit at C20 divided by 5 at the 20-hour rate. For this block's 93.2 Ah that is 18.6 amps per unit. A rectifier that can source more than that into a recovering string will run the plates hot, and the excess does nothing for recharge time once the block starts accepting less current on its own.
What ambient does C&D call nominal for this block?
+74°F to +80°F, which is +23°C to +27°C. That is the room band C&D asks for, and it is a separate figure from the rating temperature: the 93.2 Ah and the 350 watts per cell are both taken at 77°F (25°C), and the 10 year design life is quoted at 25°C. A cabinet that runs above that band keeps working, and the ratings on this page stop describing it. Send the average ambient with the quote request and a specialist notes it.
How cold or hot can a UPS12-350MR run?
C&D publishes a discharge range of -40°F to +160°F, which is -40°C to +71°C, and a charge range of -10°F to +140°F, or -23°C to +60°C, with temperature compensation. Operating cool cuts the discharge time available, so a shelter that swings below freezing needs the runtime checked at the low end rather than at 77°F.
Send the quantity, your delivery ZIP and your requested-by date. A specialist confirms availability, the warranty term, volume pricing and freight in writing, with no obligation to buy.
Call 1-877-775-4381 · battery specialists, not a call centerWARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov (State of California only).