C&D Technologies UPS12-210MR Battery

$234.00
SKU: UPS12-210MR
Availability: Request Quote For Availability
Minimum Purchase: 6 units
Shipping: Free shipping on orders $75 and up
Voltage: 12
Capacity: 53.8 Ah (20-hour rate to 1.75 VPC at 25C); 206 W per cell at 15 minutes to 1.67 VPC
Chemistry: AGM VRLA, high rate, long life alloy
Terminal: Top terminal, threaded insert, 10-32 UNF, 30 in-lbs
Minimum Order Quantity: 4 Batteries
Dimensions: 9.00 x 5.48 x 8.07 in
C&D Technologies UPS12-210MR Battery

C&D Technologies UPS12-210MR Battery

$234.00
Adding to cart… The item has been added

C&D Dynasty UPS12-210MR Battery - 12V 53.8 Ah High Rate Max AGM

This part is retired by C&D. C&D names the UPS12-215PLP Pure Lead Plus as the replacement; ask a specialist to price the PLP. We supply the UPS12-210MR while inventory holds.
Terminal hardware changes at the UPS12-210MR: it is the last model C&D built with the small 10-32 UNF insert before the High Rate Max battery range moves to the 1/4-20 UNC terminal at 110 in-lbs. The ratings are 53.8 Ah at the 20-hour rate to 1.75 volts per cell at 25°C and 206 watts per cell at the 15-minute rate to 1.67 VPC. If you are matching an existing rack, your lug and wrench inventory has to change above this part.

Warranty

Warranty. C&D's term on the UPS High Rate Max series is 3 years at 25°C (77°F), under Form 41-9027. Design life is a separate figure: 10 years at 25°C is C&D's published design life for the series. Terms are confirmed in writing with your quote.

The Step Before the Quarter-Inch Terminal

53.8 Ah at the 20-hour rate
To 1.75 volts per cell at 25°C (77°F). A 55 percent step over the UPS12-150MR for 12.7 lbs and 1.24 inches of length.
206 watts per cell at 15 minutes
To 1.67 VPC at 77°F. The published table runs to 373 watts per cell at 5 minutes and 51.9 at 90 minutes, all at 77°F.
The last 10-32 terminal in the line
30 in-lbs of torque against 3,000 amps of short-circuit current. Every model above the 210MR takes a 1/4-20 UNC bolt at 110 in-lbs.
  • Patented Long Life Alloy - C&D's low-calcium grid alloy, which the sheet credits with minimizing grid growth, reducing gassing and extending battery life.
  • Bellcore 4228 recombination behavior - C&D designs the MR case around the same recombination, thermal-runaway prevention, gassing and flame-retardant characteristics as its 4228-compliant Dynasty Telecom blocks.
  • Flame retardant polypropylene to UL94-V2 - case and cover both, on a UL-recognized component that also meets UL1778, UL 924 and UL 1989.
  • Impedance 0.0045 ohms at 60 Hz - C&D prints this for reference and says plainly that individual baselines are the ones to diagnose against.
  • Air transport cleared - not restricted under IATA and ICAO Special Provisions A67, and non-hazardous per IMDG Amendment 27 by water.

Technical Specifications

C&D UPS12-210MR Specifications
Part NumberUPS12-210MR (also searched as UPS12 210MR, UPS12210MR; sold under the C&D Dynasty brand)
SeriesUPS High Rate Max (MR), retired by C&D
Battery TypeAGM, valve regulated lead acid (VRLA), high rate
Nominal Voltage12V (6 cells per unit)
Nominal Capacity53.8 Ah at the 20-hour rate to 1.75 VPC at 25°C (77°F)
Watts Per Cell206 W per cell at the 15-minute rate to 1.67 VPC at 77°F
Constant Power to 1.75 VPC341 W/cell at 5 min, 243 at 10 min, 193 at 15 min, 162 at 20 min, 123 at 30 min, 71.5 at 60 min, 50.6 at 90 min
Constant Power to 1.67 VPC373 W/cell at 5 min, 261 at 10 min, 206 at 15 min, 169 at 20 min, 127 at 30 min, 92.6 at 45 min, 73.3 at 60 min, 51.9 at 90 min
Terminal TypeTop terminal, threaded insert, 10-32 UNF
Terminal Torque30 in-lbs (4.5 N-m)
Length9.00 inches (228.6 mm)
Width5.48 inches (139.2 mm)
Height7.89 inches to case top (200.3 mm)
Total Height8.07 inches over terminals (205.1 mm)
Weight40 lbs (18 kg)
Short Circuit Current3,000 A at 0.1 second
Impedance0.0045 ohms at 60 Hz (reference figure; C&D recommends individual baselines)
Nominal Operating Temperature+74°F (+23°C) to +80°F (+27°C)
Design Life10 year design life at 25°C (C&D)
Warranty3 years at 25°C (77°F) (C&D Form 41-9027, UPS High Rate Max series)
Minimum Order4 units

Where This Battery Is Used

  • Internet housing sites - colocation suites where the string carries the cage to generator transfer.
  • Semiconductor manufacturing - tool power on lines where a dropped wafer lot is the real cost of an outage.
  • Hospital and laboratory backup - code-driven standby power that gets inspected and load-tested on a schedule.

Ordering and Freight

Minimum order is 4 units. At 40 lbs each these ship freight pre-paid by LTL to a commercial address; a residential or limited-access delivery adds $100, which is the liftgate and access charge the carrier bills us. Send the quantity, your delivery ZIP and your requested-by date, and a specialist returns a written quote with volume pricing in 24 to 48 hours.

Frequently Asked Questions

What constant power does the UPS12-210MR hold for 45 minutes?

90.3 watts per cell to 1.75 volts per cell, or 92.6 to 1.67 VPC, at 77°F. Multiply by six cells for the block and by the string count for the plant figure: twenty blocks at the 1.75 end point give roughly 10.8 kW for three quarters of an hour. C&D publishes 5, 10, 15, 20, 30, 40, 45, 50, 60 and 90 minute columns for this model at five end-point voltages.

Which C&D manual covers installing a UPS12-210MR rack?

Technical manual 41-7525, the rack-mounted installation and start-up guide for 12V VRLA batteries of 26 to 206 ampere-hour capacity. The 210MR's 53.8 Ah sits well inside that band. The guide covers battery numbering, interunit and intertier cabling, the pre-operational checks and the initial freshening charge, and it points to Form 41-7471 for the operational qualification checklist.

How much space goes between blocks on the shelf?

Half an inch (1.27 cm) between units, per C&D's installation guide. The gap does two jobs: it lines the interunit cables up with the adjacent terminals, and it lets convection carry heat away from the cases. Place all the blocks on a tier with the same polarity to the front, and load the lowest tiers first for rack stability.

What impedance reading should a new UPS12-210MR show?

C&D publishes 0.0045 ohms at 60 Hz for this model and marks the figure for reference only, recommending individual baselines for diagnostic work. Take your own readings at installation, log them per battery number, and trend the drift rather than the absolute value. C&D's technical bulletin 41-7271 covers impedance and conductance testing method.

Next rating up: C&D UPS12-300MR78.6 Ah and 300 watts per cell at 15 minutes, on the 1/4-20 UNC terminal at 110 in-lbs.
Get the UPS12-210MR priced for your string

Send the quantity, your delivery ZIP and your requested-by date. A specialist confirms availability, the warranty term, volume pricing and freight in writing, with no obligation to buy.

Call 1-877-775-4381  ·  battery specialists, not a call center

WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov (State of California only).

Customer Reviews

Customers Also Viewed