• Free Shipping

    Orders $75 & Up

  • 30-day Money Back

    Guarantee*

  • 100% Secure Online Shopping

    SSL - Verified Merchant

C&D UPS12-355PLP Pure Lead Plus Battery

$335.95
SKU: UPS12-355PLP
Availability: Request Quote For Availability
Minimum Purchase: 4 units
Shipping: Free shipping on orders $75 and up
Voltage: 12
Capacity: 94 Ah (C20, 20-hour rate to 1.75 VPC at 25C); 365.5 W per cell at 15 minutes to 1.67 VPC
Chemistry: AGM VRLA, pure lead, long-life alloy grids
Terminal: Top terminal, threaded insert, 1/4-20 UNC, 110 in-lbs
Features: Pure Lead
Dimensions: 12.0 x 6.8 x 8.1 in
C&D UPS12-355PLP Pure Lead Plus Battery

C&D UPS12-355PLP Pure Lead Plus Battery

$335.95
Adding to cart… The item has been added

C&D Dynasty UPS12-355PLP Battery - 12V 94 Ah Pure Lead Plus AGM

The short end of the discharge table is where the UPS12-355PLP earns its place, the Pure Lead Plus block C&D names for the retired UPS12-350MR, rated 94 Ah at the 20-hour rate to 1.75 volts per cell at 25°C. C&D prints constant power for this model at one, two, three and four minutes as well as the familiar fifteen, and specifies the Pure Lead Plus construction to take runtimes under five minutes without giving up standby life. A modern UPS module that transfers to generator in ninety seconds is discharging in exactly that window, and 1,045.0 watts per cell is what the block holds for the first minute of it.

Warranty

Warranty. C&D's term on the Pure Lead Plus series is 5 years at 30°C (86°F), under C&D's Pure Lead Plus limited warranty (2021). Design life is a separate figure: C&D publishes a 12+ year design life at 25°C (77°F) for the series. Terms are confirmed in writing with your quote.

Power Below Five Minutes

1,045.0 watts per cell at one minute
To 1.67 volts per cell at 77°F. Six cells to a block, so 6,270 watts out of a single unit for the first sixty seconds.
365.5 watts per cell at fifteen minutes
To 1.67 VPC, or 339.7 to 1.75 VPC. The column most UPS ride-through tables land on, with 685.3 at five minutes above it.
Five end points on one table
1.75, 1.70, 1.67, 1.65 and 1.60 volts per cell. The four lower columns run from 1 minute to 60; the 1.75 column starts at 5 minutes.
  • Specified for sub-five-minute duty - C&D designs the Pure Lead Plus series to handle runtimes under five minutes safely without trading away long-term performance.
  • Patented long-life grid alloy - C&D's alloy is specified to hold grid growth and gassing down across the float service life.
  • 4,200 amps short-circuit current - at 0.1 second, the figure the DC breaker and fuse coordination on this string gets checked against.
  • UL 94 V-2 and UL 94 V-0 materials - the flammability ratings C&D lists for the series, alongside UL 1973 for stationary energy storage.
  • Threaded inserts on the cover face - taking a 1/4-20 UNC bolt at 110 in-lbs (12.4 N-m), set with a torque wrench, never by feel.

Technical Specifications

C&D UPS12-355PLP Specifications
Part NumberUPS12-355PLP (also searched as UPS12 355PLP, UPS12355PLP; replaces UPS12-350MR; sold under the C&D Dynasty brand)
SeriesPure Lead Plus (PLP), top terminal
Battery TypeAGM, valve regulated lead acid (VRLA), pure lead
Nominal Voltage12V (6 cells per unit)
Capacity, C2094 Ah at the 20-hour rate to 1.75 VPC at 25°C (77°F)
Capacity, C888 Ah at the 8-hour rate to 1.75 VPC at 25°C
Capacity, C1083 Ah at the 10-hour rate to 1.80 VPC at 20°C
Constant Power, 15 minutes365.5 W per cell to 1.67 VPC at 77°F; 339.7 W per cell to 1.75 VPC
Constant Power to 1.67 VPC1,045.0 W/cell at 1 min, 905.0 at 2 min, 811.2 at 3 min, 728.3 at 4 min, 685.3 at 5 min, 471.7 at 10 min, 365.5 at 15 min, 292.5 at 20 min, 218.3 at 30 min, 158.4 at 45 min, 124.3 at 60 min
Constant Power to 1.70 VPC1,005.9 W/cell at 1 min, 659.2 at 5 min, 454.0 at 10 min, 352.8 at 15 min, 283.2 at 20 min, 212.5 at 30 min, 122.3 at 60 min
Constant Power to 1.60 VPC1,153.7 W/cell at 1 min, 725.6 at 5 min, 495.6 at 10 min, 381.4 at 15 min, 303.5 at 20 min, 126.0 at 60 min
Constant Current to 1.75 VPC62.8 A for 1 hour, 16.8 A for 5 hours, 11.0 A for 8 hours, 9.0 A for 10 hours, 4.7 A for 20 hours, 4.0 A for 24 hours
Short Circuit Current4,200 A at 0.1 second
Terminal TypeTop terminal, threaded insert, 1/4-20 UNC
Terminal Torque110 in-lbs (12.4 N-m)
Length306 mm (12.0 inches)
Width173 mm (6.8 inches)
Height203 mm (8.0 inches)
Total Height205 mm (8.1 inches) over terminals
Weight67 lbs (30.4 kg)
Design Life12+ years at 25°C (77°F) (C&D)
Warranty5 years at 30°C (86°F) (C&D Pure Lead Plus limited warranty, 2021)
Minimum Order4 units

Where This Battery Is Used

  • High-density UPS modules - cabinets designed around a ride-through of five minutes or less with the generator starting straight away.
  • Broadcast and land mobile radio sites - transmitter control and studio plant held on a maintained float charge.
  • Automatic transfer switch backup - critical panels carried while the transfer switch picks up.

Ordering and Freight

Minimum order is 4 units, at 67 lbs a block. Sets move freight pre-paid by LTL to a commercial address; a residential or limited-access delivery adds $100, which is the liftgate and access charge the carrier bills us. Send the quantity, your delivery ZIP and your requested-by date, and a specialist returns a written quote with volume pricing in 24 to 48 hours.

Frequently Asked Questions

How much power does a UPS12-355PLP hold for one minute?

1,045.0 watts per cell to 1.67 volts per cell at 77°F, which is 6,270 watts from one block. To a 1.70 end point the figure is 1,005.9, and to 1.60 it rises to 1,153.7. A forty-block 480 VDC string therefore carries roughly 251 kW for that first minute at the 1.67 end point. Two minutes brings it down to 905.0 watts per cell, three to 811.2 and four to 728.3.

Does a short discharge wear this battery faster?

C&D specifies the Pure Lead Plus construction for safe handling of runtimes under five minutes without sacrificing long-term performance, which is why the series publishes rates down to one minute in the first place. Where the block you are comparing against does not publish below five minutes, there is no published figure to size that duty against. Send the discharge profile with your quote request and a specialist checks it against the published table.

What does the UPS12-355PLP do on a long, low-current discharge?

16.8 amps for five hours, 11.0 amps for eight, 9.0 amps for ten, 4.7 amps for twenty and 4.0 amps for twenty-four, all to 1.75 volts per cell at 77°F. Those are the rows to use for a telemetry cabinet or a control load that draws steadily rather than in a burst. C&D also publishes a 1.80 VPC current table if your plant alarms at a higher end point.

Is the UPS12-355PLP the same case as the UPS12-405PLP?

No. They share the 173 mm width, but the 405PLP is 341 mm long against 306 and 216 mm over the terminals against 205, and it weighs 76 lbs against 67. A tray cut for the 355PLP will not take the 405PLP without gaining 35 mm of length and 11 mm of height. Going the other way, a 405PLP shelf holds a 355PLP with room to spare, though the restraint bar will need repositioning.

Next rating up: C&D UPS12-405PLP104 Ah at the 20-hour rate and 402.4 watts per cell at fifteen minutes, on the case C&D matched to the retired UPS12-400MR.
Get the UPS12-355PLP priced for your string

Send the quantity, your delivery ZIP and your requested-by date. A specialist confirms availability, the warranty term, volume pricing and freight in writing, with no obligation to buy.

Call 1-877-775-4381  ·  battery specialists, not a call center

WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov (State of California only).

Customer Reviews

Customers Also Viewed