Leoch XP12-150FR High Rate AGM Battery
Leoch XP12-150FR High Rate AGM Battery
Leoch XP12-150FR Battery - 12V 150 W per Cell High Rate AGM, 35Ah, M6
Warranty
The M6 Block for Mid-Size Rack UPS
- 162.7 amps for 5 minutes - to 1.67 volts per cell, with 80.0 amps at 15 minutes and 26.4 amps for a full hour.
- 35 Ah at the 20-hour rate - to 1.80 volts per cell at 25°C, 1.75 amps for 20 hours, the figure to use if the block is ever asked to run a long, light load.
- 980 amps short-circuit current - at approximately 8 milliohms internal resistance, fully charged, for DC-side protection sizing.
- Virgin lead plates, copper alloy inserts - low resistance at the plates and at the posts, so the voltage holds under load instead of sagging into the inverter's low-volt cutoff.
- 100 percent capacity tested - every XP block is discharge tested and matched on voltage and internal resistance before it leaves the plant.
Technical Specifications
| Leoch XP12-150FR Specifications | |
|---|---|
| Part Number | XP12-150FR (also written XP12-150, XP12 150, xp12-150fr and leoch xp12-150) |
| Series | Leoch XP, ultra high rate AGM for UPS, flame retardant (FR) case build |
| Battery Type | High rate AGM, valve regulated lead acid (VRLA), UPS standby service |
| Nominal Voltage | 12V (6 cells) |
| Nominal Rating, 15 Minutes | 150 W per cell to 1.67 VPC at 25°C (900 W per battery) |
| Capacity, 20-Hour Rate | 35 Ah to 1.80 VPC at 25°C |
| Discharge Current, 5 Minutes | 162.7 A to 1.67 VPC; 142.5 A to 1.80 VPC |
| Discharge Current, 15 Minutes | 80.0 A to 1.67 VPC; 73.2 A to 1.80 VPC |
| Discharge Current, 1 Hour | 26.4 A to 1.67 VPC; 25.0 A to 1.80 VPC |
| Discharge Power, 5 Minutes | 296.1 W per cell to 1.67 VPC |
| Discharge Power, 1 Hour | 50.7 W per cell to 1.67 VPC |
| Short Circuit Current | 980 A |
| Internal Resistance | Approximately 8 milliohms, fully charged, at 25°C |
| Maximum Charge Current | 0.25C (8.75 A) at 25°C |
| Float Charge Voltage | 2.25 to 2.30 V per cell at 25°C (13.5 to 13.8 V per battery) |
| Equalization Charge Voltage | 2.30 to 2.40 V per cell at 25°C |
| Temperature Coefficient | -3 mV per cell per °C on float; -4 mV per cell per °C on equalize |
| Terminal Type | M6 threaded insert (Leoch T6-I) |
| Length | 195 mm (7.68 inches) |
| Width | 130 mm (5.12 inches) |
| Container Height | 164 mm (6.46 inches) |
| Total Height | 167 mm (6.57 inches) |
| Weight | 10.44 kg (23.0 lbs) |
| Operating Temperature | Discharge -15°C to 50°C (5°F to 122°F); charge -20°C to 40°C (-4°F to 104°F); storage -15°C to 40°C (5°F to 104°F) |
| Capacity vs Temperature | 106% at 40°C; 100% at 25°C; 86% at 0°C |
| Self Discharge | 3% per month or less at 25°C |
| Container Material | ABS, flame retardant to UL 94 V-0 (the FR build; UL 94 HB is Leoch's standard case) |
| Standards | IEC 60896-21 and -22, third party tested; UL recognized; CE; IATA approved for air freight; IATF 16949 plants |
| Design Life | 12 years at 25°C on float service (Leoch) |
| Warranty | 36 months in UPS service (Leoch, XP) |
Where This Battery Is Used
- Rack-mount UPS, 2 to 6 kVA - the network room and small server room systems whose internal battery trays are built around a 7.7 by 5.1 inch block with M6 hardware.
- Hospital and laboratory equipment - Leoch lists both among the XP applications: instruments that must ride through a transfer without a reset.
- Emergency lighting and egress inverters - code-driven backup in occupied buildings, where the V-0 case rating is commonly specified.
Ordering and Freight
Frequently Asked Questions
What warranty applies, and is the 12-year figure part of it?
Leoch warrants the XP line for 36 months in UPS service. The 12 years is design life, Leoch's estimate of float service at 25°C from the XP12-150 datasheet, and it carries no replacement commitment. Both figures appear on this page, always labeled, because a listing that runs them together is how a buyer ends up believing in a 12-year warranty. The term is confirmed in writing with your quote.
What does the 150 in XP12-150FR stand for?
Watts per cell over a 15-minute discharge to 1.67 volts per cell at 25°C. Leoch names every XP part by this rating rather than by amp hours because the range exists for UPS duty, and a UPS is sized on power over minutes. Six cells make about 900 watts from one block for 15 minutes. The 35 Ah figure, at the 20-hour rate, is on the sheet as well, and it is the number to use only if the block is ever asked to run a long, light load.
Can the XP12-150FR replace a 35 Ah general purpose battery of the same size?
Physically, often; in a UPS, the swap is usually an upgrade. A general purpose 35 Ah AGM in a 195 by 130 mm case delivers far less of its capacity in 15 minutes than this block does, because its plates were drawn for hours of light load rather than minutes of heavy load. Compare the watts per cell at your runtime and end voltage, not the amp hour labels, and check that the terminal is M6. If the outgoing battery has a different insert or a post, send a photo of it and the quote will state what hardware is needed.
How fast does it recharge after an outage?
Leoch caps the charge current at 0.25C, about 8.75 amps for this block, so recharge time depends on the depth of the discharge and on the charger's own limit, which in most UPS units is lower still. As a working rule, a string is back in the high nineties of capacity after a day on the rectifier's normal recharge setting. If your site runs a short generator-test interval that discharges the string often, tell the specialist, because repeated discharges without a full recharge shorten the life of any VRLA battery.
Send the UPS model, the quantity and your delivery ZIP. A specialist confirms the 195 by 130 mm footprint against the tray, checks the M6 hardware, and quotes the set with lead time and freight in writing.
Call 1-877-775-4381 · battery specialists, not a call centerWARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov (State of California only).