• Free Shipping

    Orders $75 & Up

  • 30-day Money Back

    Guarantee*

  • 100% Secure Online Shopping

    SSL - Verified Merchant

Leoch XP12-490FR High Rate AGM Battery

$398.00
SKU: XP12-490FR
Availability: Request Quote For Availability
Shipping: Free shipping on orders $75 and up
Voltage: 12
Capacity: 142 Ah (20-hour rate to 1.80 VPC at 25C); 490 W per cell (15-min to 1.67 VPC)
Chemistry: High rate AGM VRLA (UPS standby)
Terminal: M6 threaded insert (Leoch T8)
Dimensions: 13.2 x 6.77 x 10.9 in (L x W x total H); 335 x 172 x 278 mm
Design Life: 12 years at 25C on float (Leoch)
Features: High rate AGM, 3,264 A short circuit, 3.8 mOhm, -15C to 50C discharge, UL 94 V-0 FR case, IEC 60896-21/22, 36-month Leoch UPS term
Group Size: Not published by Leoch; 335 x 172 mm tall XP case shared with XP12-540FR
Leoch XP12-490FR High Rate AGM Battery

Leoch XP12-490FR High Rate AGM Battery

$398.00
Adding to cart… The item has been added

Leoch XP12-490FR Battery - 12V 490 W per Cell High Rate AGM, 142Ah, M6

The XP12-490FR is the lower of the two ratings Leoch builds in its tall XP case: 490 watts per cell over 15 minutes to 1.67 volts per cell, about 2,940 watts from the 12 volt block, with 142 Ah at the 20-hour rate. The case is 335 by 172 mm and 278 mm to the top of the M6 terminals (13.2 by 6.77 by 10.9 inches) at 42.6 kg (93.9 lbs). The FR in the part number is the UL 94 V-0 flame retardant case build. Against the XP12-400FR in the low case it adds 62 mm of height, 40 Ah and 90 watts per cell on nearly the same floor area. Internal resistance is about 3.8 milliohms, the 5-minute row of the discharge table reaches 426 amps, and the design life is 12 years at 25°C on float. Quoted in sets of four or more.

Warranty

Warranty. Leoch warrants the XP line for 36 months in UPS service. Design life is a separate figure: 12 years at 25°C (77°F) on float, from the XP12-490 datasheet, and it is not a warranty period. Terms are confirmed in writing with your quote.

More Runtime on the Same Floor Space

490 watts per cell at 15 minutes
About 2,940 watts from one block to 1.67 volts per cell, and 777.5 watts per cell at the 5-minute point where a generator-backed plant does its bridging.
142 Ah on a 335 by 172 mm footprint
Forty percent more capacity than the XP12-400FR, bought with 62 mm of height rather than extra floor, on a shelf that has the vertical clearance.
UL 94 V-0 case
The FR build. Leoch lists UL 94 HB as the standard XP case and V-0 as the option; this page sells the V-0 option that data center and hospital specifications call for.
  • 426.0 amps for 5 minutes - to 1.67 volts per cell, with 270.7 amps at 15 minutes, 168.3 amps at 30 minutes and 99.4 amps for a full hour.
  • 142 Ah at the 20-hour rate - to 1.80 volts per cell at 25°C, 7.10 amps for 20 hours, for the rare site that runs it as a long-duration reserve.
  • 3,264 amps short-circuit current - at approximately 3.8 milliohms internal resistance, fully charged, the highest in the XP range and the figure the DC-side breaker coordination needs.
  • Virgin lead plates, copper alloy inserts - low resistance at the plates and the posts, so the voltage holds under load instead of sagging into the inverter's cutoff.
  • 100 percent capacity tested - every XP block is discharge tested and matched on voltage and internal resistance before it leaves the plant.

Technical Specifications

Leoch XP12-490FR Specifications
Part NumberXP12-490FR (also written XP12-490, XP12 490, xp12-490fr and leoch xp12-490)
SeriesLeoch XP, ultra high rate AGM for UPS, flame retardant (FR) case build
Battery TypeHigh rate AGM, valve regulated lead acid (VRLA), UPS standby service
Nominal Voltage12V (6 cells)
Nominal Rating, 15 Minutes490 W per cell to 1.67 VPC at 25°C (2,940 W per battery)
Capacity, 20-Hour Rate142 Ah to 1.80 VPC at 25°C
Discharge Current, 5 Minutes426.0 A to 1.67 VPC; 310.5 A to 1.80 VPC
Discharge Current, 15 Minutes270.7 A to 1.67 VPC; 216.5 A to 1.80 VPC
Discharge Current, 30 Minutes168.3 A to 1.67 VPC; 144.4 A to 1.80 VPC
Discharge Current, 1 Hour99.4 A to 1.67 VPC; 87.2 A to 1.80 VPC
Discharge Power, 5 Minutes777.5 W per cell to 1.67 VPC
Discharge Power, 1 Hour191.8 W per cell to 1.67 VPC
Short Circuit Current3,264 A
Internal ResistanceApproximately 3.8 milliohms, fully charged, at 25°C
Maximum Charge Current0.25C (35.5 A) at 25°C
Float Charge Voltage2.25 to 2.30 V per cell at 25°C (13.5 to 13.8 V per battery)
Equalization Charge Voltage2.30 to 2.40 V per cell at 25°C
Temperature Coefficient-3 mV per cell per °C on float; -4 mV per cell per °C on equalize
Terminal TypeM6 threaded insert (Leoch T8)
Length335 mm (13.2 inches)
Width172 mm (6.77 inches)
Container Height275 mm (10.8 inches)
Total Height278 mm (10.9 inches)
Weight42.6 kg (93.9 lbs)
Operating TemperatureDischarge -15°C to 50°C (5°F to 122°F); charge -20°C to 40°C (-4°F to 104°F); storage -15°C to 40°C (5°F to 104°F)
Capacity vs Temperature106% at 40°C; 100% at 25°C; 86% at 0°C
Self Discharge3% per month or less at 25°C
Container MaterialABS, flame retardant to UL 94 V-0 (the FR build; UL 94 HB is Leoch's standard case)
StandardsIEC 60896-21 and -22, third party tested; UL recognized; CE; IATA approved for air freight; IATF 16949 plants
Design Life12 years at 25°C on float service (Leoch)
Warranty36 months in UPS service (Leoch, XP)

Where This Battery Is Used

  • Large three-phase UPS strings - the 100 kVA and larger data center and hospital systems whose external battery cabinets are shelved for a 13.2 by 6.8 inch block about 11 inches tall.
  • Generator-backed plants - sites where the string only carries the load until the set is on line, and the 5-minute figure of 426 amps is the one that matters.
  • Telecommunications DC plants - on Leoch's XP application list: the reserve behind switching equipment in occupied buildings, where the V-0 case rating is specified.

Ordering and Freight

Sold in a minimum of four units. Four XP12-490FR come to about 375 lbs on a pallet and ship by LTL freight; a residential or limited-access address adds $100 for the liftgate and access charge the carrier passes through. Send the quantity, your delivery ZIP and your requested-by date. A specialist confirms availability, lead time, volume pricing and freight in writing in 24 to 48 hours.

Frequently Asked Questions

What warranty applies, and is the 12-year figure part of it?

Leoch warrants the XP line for 36 months in UPS service. The 12 years is design life, Leoch's estimate of float service at 25°C from the XP12-490 datasheet, and it carries no replacement commitment. Both figures appear on this page, always labeled, because a listing that runs them together is how a buyer ends up believing in a 12-year warranty. The term is confirmed in writing with your quote.

XP12-490FR or XP12-540FR: they look identical.

They are, on the outside. Both stand on the same 335 by 172 by 278 mm case with the same M6 insert, and the weights are within a quarter of a pound of each other. The difference is inside: the XP12-540FR is plated for 540 watts per cell and 155 Ah against 490 watts and 142 Ah here, about 10 percent more of both. If your UPS runtime table calls for the 490 rating, this is the part; if the string is marginal at 490, the 540 goes into the same shelf with no rework. Either way, do not mix the two in one string.

Can the XP12-490FR replace the XP12-400FR in my cabinet?

Only if the shelf pitch takes it. The XP12-490FR is 278 mm (10.9 inches) tall against 216 mm (8.50 inches) for the XP12-400FR, about 2.5 inches more, and the footprint grows from 325.5 by 170 mm to 335 by 172. If the cabinet clears that height, the step from 400 to 490 watts per cell runs the same load roughly 20 percent longer. If it was shelved for the 8.5 inch block, stay with the XP12-400FR and add runtime with a second string.

How long can it sit in stores before installation?

Leoch's XP sheet puts self discharge at 3 percent per month or less at 25°C, and the storage temperature range at -15°C to 40°C. Check the open circuit voltage on receipt and log it, then check again at intervals, and give the block a freshening charge before it is installed if it has sat for months or if the voltage has fallen. Warm storage shortens the interval. A block that has sat past its limit without a charge is a maintenance question rather than a warranty one, so if the install date is uncertain, ask the specialist to put a commissioning charge recommendation on the quote.

Same case, top rating: Leoch XP12-540FR540 watts per cell and 155 Ah on the identical 335 by 172 by 278 mm footprint at 93.5 lbs.
Not sure the XP12-490FR clears your shelf?

Send the shelf height, the UPS model and the quantity. A specialist confirms the fit against the 278 mm total height, checks the M6 hardware, and quotes the set with lead time and freight in writing.

Call 1-877-775-4381  ·  battery specialists, not a call center

WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov (State of California only).

Customer Reviews