Free Shipping
Orders $75 & Up
-
30-day Money Back
Guarantee*
-
100% Secure Online Shopping
SSL - Verified Merchant
12V 180AH CSB TPL121800 Front Terminal Battery for Telecom Power
12V 180AH CSB TPL121800 Front Terminal Battery for Telecom Power
CSB TPL121800 Battery - 12V 192 Ah Front Terminal Telecom AGM
Warranty
More Reserve in the Same Rack Position
- 192 Ah at the 20 hour rate and 175 Ah at the 8 hour rate - both to 1.75 volts per cell at 25°C; telecom reserve calculations conventionally read the 8 hour column.
- 54 amps maximum charge current - 12.5 percent above the TPL121600, so recharge time after an event holds despite the extra capacity.
- 800 amps maximum discharge - the same ceiling CSB publishes across the TPL range, from the 121000 upward.
- 2,575 amps short circuit current and 3.90 milliohms - CSB publishes 2,593 amps and 3.70 milliohms for the smaller TPL121600, so on those two rows this block reads marginally weaker while every discharge column reads stronger.
- Float held 13.5 to 13.8 VDC per battery - measured at 25°C (77°F); the equalization window runs 14.4 to 15.0 VDC per battery at that same temperature.
Technical Specifications
| CSB TPL121800 Specifications | |
|---|---|
| Part Number | TPL121800 (also searched as TPL 121800, TPL121800FR and tpl121800; CSB prints the flame retardant build as TPL 121800FR) |
| Series | TPL, telecom front access, 12 volt front terminal |
| Battery Type | AGM, valve regulated lead acid (VRLA), pure lead construction |
| Nominal Voltage | 12V |
| Capacity, 20-Hour Rate | 192 Ah to 1.75 VPC at 25°C (77°F) |
| Capacity, 8-Hour Rate | 175 Ah to 1.75 VPC at 25°C |
| Capacity, 8-Hour Rate to 1.80 VPC | 172 Ah at 25°C |
| Watts Per Cell, 15 Minutes | 535 W to 1.67 VPC at 25°C (3,208 W per block) |
| Watts Per Cell, 30 Minutes | 370 W to 1.67 VPC at 25°C |
| Watts Per Cell, 60 Minutes | 231 W to 1.67 VPC at 25°C |
| Discharge, 15 Minutes | 307 A to 1.67 VPC at 25°C |
| Discharge, 8 Hours | 21.8 A to 1.75 VPC at 25°C |
| Maximum Charge Current | 54 A |
| Maximum Discharge Current | 800 A |
| Short Circuit Current | 2,575 A |
| Internal Resistance | Approximately 3.90 milliohms |
| Terminal Type | I2 threaded lead alloy insert, accepts an M6 bolt |
| Terminal Torque | 44.9 ±9.0 lbf-in (51.7 ±10.3 kgf-cm, 5.1 ±1.0 N-m) |
| Length | 21.54 inches (547.0 mm) |
| Width | 4.94 inches (124.8 mm) |
| Height | 12.72 inches (320.3 mm) |
| Weight | 121.44 lbs (55.1 kg) |
| Rack Format | 23 inch front terminal |
| Float Charging Voltage | 13.5 to 13.8 VDC per battery at 25°C (77°F) |
| Equalization Charging Voltage | 14.4 to 15.0 VDC per battery at 25°C (77°F) |
| Operating Temperature | Nominal 25°C (77°F); discharge -15°C to 50°C (5°F to 122°F); charge and storage -15°C to 40°C (5°F to 104°F) |
| Self Discharge | Less than 10 percent after 90 days at 25°C; storable to six months before a full recharge |
| Container Material | Flame retardant ABS (UL 94-V0) |
| Standards | IEC 60896-21/22:2004; UL1973 Listed (MH66728); UL1989 Recognized (MH14533); TUV NORD to ISO 9001:2015 |
| Design Life | Up to 12 years in standby service at 25°C; greater than 12 years on the Eurobat 20°C basis |
| Warranty | 3 years (CSB, TPL front terminal range) |
| Country of Origin | Taiwan |
Where This Battery Is Used
- 23 inch telecom relay racks - four block strings on a -48 volt bus, sized on the 8 hour column and installed with both posts facing the aisle.
- Outside plant cabinets and huts - remote sites where a maintenance visit is expensive and the 12 year design life is the reason for the specification.
- Cable headends and edge facilities - installations holding a transfer window measured in minutes rather than hours, sized on the 15 minute column.
Ordering and Freight
Frequently Asked Questions
TPL121800 or TPL121600?
The case is the same, so the decision is purely about reserve and cost. The 121800 gives 175 Ah at the 8 hour rate against 159, and 535 watts per cell at 15 minutes against 445, for 0.66 lbs more. Where the rack position is already committed and the reserve target has crept up, the larger block is the straightforward answer. Where the site comfortably meets its target today, the 121600 is the right specification and we will quote it that way.
What does the 1800 in the part number mean?
It is a nominal amp hour designation applied at the catalog level. CSB publishes two measured ratings, 192 Ah at the 20 hour rate and 175 Ah at the 8 hour rate, and 180 sits between them. Which side of it you land on depends entirely on how hard you draw the block. Size from the column that matches your discharge duration and treat the badge as a catalog label.
Will it fit a 19 inch rack?
No. The block is 21.54 inches long and CSB classes it as a 23 inch front terminal part, as it does the TPL121600 and the TPL122000. For a 19 inch relay rack the TPL121000 is the corresponding part at 20.16 inches long and 100 Ah on the 8 hour rate. Confirm the rack width before ordering, because the two families do not interchange.
Why is internal resistance higher than on the smaller TPL121600?
That is what CSB publishes: 3.90 milliohms here against 3.70 for the 121600, both quoted as approximate, and short circuit current of 2,575 amps against 2,593. Every discharge column runs the other way, with this block ahead at every duration from 15 minutes to 20 hours. We report both figures as printed rather than dropping the two that read less well. If your design turns on the fault current figure, ask a specialist to confirm it with CSB in writing.
Send the part number in the rack today, the block count and the reserve you have to hold. A specialist checks the fit against the shelf and quotes the string and freight in writing.