CSB TPL121500 12V 150AH Sealed Battery - Telecom Power & UPS Applications
CSB TPL121500 12V 150AH Sealed Battery - Telecom Power & UPS Applications
CSB TPL121500 Battery - Superseded by the TPL121600, 12V Front Terminal Telecom
What the TPL121600FR Gives You Instead
- Our record carries this part as MPN TPL121500A - the A revision, which is the form buyers most often have stamped on the label they are replacing.
- 800 amps maximum discharge on the replacement - the same ceiling CSB publishes across the TPL front terminal range.
- 48 amps maximum charge current - the recharge ceiling per block, which is what sizes the rectifier plant after an event.
- 12 year design life at 25°C (77°F) - unchanged between the old part and its replacement, and the reason the range is specified for remote sites.
- Both posts face the aisle - torque checks and resistance readings happen at the rack face rather than by pulling a 120 pound block off the shelf.
Warranty on the Replacement
TPL121600FR Specifications
| CSB TPL121600FR, the replacement for the TPL121500 | |
|---|---|
| Superseded Part Numbers | TPL121500, TPL121500A and TPL121500AFR (also written TPL 121500 and tpl121500) |
| Replacement Part Number | TPL121600FR (also written TPL121600 and TPL 121600) |
| Series | TPL, telecom front access, 12 volt front terminal |
| Battery Type | AGM, valve regulated lead acid (VRLA), pure lead construction |
| Nominal Voltage | 12V |
| Capacity, 8-Hour Rate | 159 Ah to 1.75 VPC at 25°C (77°F) |
| Capacity, 20-Hour Rate | 173 Ah to 1.75 VPC at 25°C |
| Capacity, 8-Hour Rate to 1.80 VPC | 156 Ah at 25°C |
| Watts Per Cell, 15 Minutes | 445 W to 1.67 VPC at 25°C (2,672 W per block) |
| Maximum Charge Current | 48 A |
| Maximum Discharge Current | 800 A |
| Short Circuit Current | 2,593 A |
| Internal Resistance | Approximately 3.70 milliohms |
| Terminal Type | Front terminal, I2 threaded lead alloy insert accepting an M6 bolt |
| Terminal Torque | 44.9 ±9.0 lbf-in (51.7 ±10.3 kgf-cm, 5.1 ±1.0 N-m) |
| Length | 21.54 inches (547.0 mm) |
| Width | 4.94 inches (124.8 mm) |
| Height | 12.72 inches (320.3 mm) |
| Weight | 120.78 lbs (54.80 kg) |
| Rack Format | 23 inch front terminal |
| Float Charging Voltage | 13.5 to 13.8 VDC per battery at 25°C (77°F) |
| Equalization Charging Voltage | 14.4 to 15.0 VDC per battery at 25°C (77°F) |
| Operating Temperature | Nominal 25°C (77°F); discharge -15°C to 50°C (5°F to 122°F); charge and storage -15°C to 40°C (5°F to 104°F) |
| Container Material | Flame retardant ABS (UL 94-V0) |
| Standards | IEC 60896-21/22:2004; UL1973 Listed (MH66728); UL1989 Recognized (MH14533); TUV NORD to ISO 9001:2015 |
| Design Life | Up to 12 years in standby service at 25°C; greater than 12 years on the Eurobat 20°C basis |
| Warranty | 3 years (CSB, TPL front terminal range) |
| Country of Origin | Taiwan |
Where the TPL121500 Was Used
- 23 inch telecom relay racks - four block strings on a -48 volt bus, where the reserve figure was written against the 8 hour column.
- Outside plant cabinets and huts - remote sites chosen for the 12 year design life because a maintenance visit costs more than the battery.
- Cable headends and edge facilities - plant holding a transfer window while the generator picks up the site.
Ordering the Replacement
Frequently Asked Questions
Can I still buy a TPL121500?
Not as new stock from CSB. The number has come out of the current telecom front terminal range and the TPL121600FR occupies that position now. If you have a partly populated string and you need the old part specifically to finish it, say so on the quote request and a specialist will tell you honestly whether any remains findable, and will name the substitute if the answer is no.
What is the difference between TPL121500 and TPL121500A?
The A is CSB's revision suffix on this line, the same convention that produced the TPL121250A. Our own catalog record for this listing carries the manufacturer part number as TPL121500A, so the label on most units in the field will read that way. An FR suffix on top of it denotes the flame retardant case. All three forms describe the same superseded position in the range.
Will the TPL121600 sit in my existing tray?
Usually, and the reason for the hedge is documented rather than defensive. CSB has revised this case more than once and the width and height printed on older sheets sit a couple of millimeters away from the current figures, which is nothing on most shelves and decisive on a tight one. The current block is 21.54 by 4.94 inches and 12.72 inches tall. Measure the opening, send the number, and it gets confirmed before the order goes in.
Do I have to replace the whole string at once?
Yes, and we would rather lose the smaller order than tell you otherwise. A string charges and discharges as one unit, so mixing an older block with new ones leaves the whole bank governed by the weakest section and pulls the new blocks down toward the old ones. Replacing four of eight saves money this year and usually costs a full string inside two. Budget for the bank rather than the block.
Send the block count, the tray dimensions and the reserve you have to hold. A specialist confirms the fit against your rack and quotes the replacement string and freight in writing.
Call 1-877-775-4381 · battery specialists, not a call centerWARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov (State of California only).