CSB HR12120WFR 12V High Rate AGM VRLA Battery for UPS Applications
CSB HR12120WFR 12V High Rate AGM VRLA Battery for UPS Applications
CSB HR12120WFR Battery - 12V 123W Per Cell High Rate AGM
Warranty
The Largest Block in the HR Range
- 30 Ah at the 20 hour rate - per the CSB price list; the per-part datasheet rates this series in watts per cell rather than amp hours, so the two documents answer different questions.
- 67.0 amps at the 15 minute rate - to 1.67 volts per cell, rising to 124 amps over 5 minutes and 88.9 amps over 10.
- 12 amps maximum charge current - the recharge ceiling per block, and what the rectifier gets sized on across a long string.
- 225 amps maximum discharge current - lower than the smaller HR1290WFR at 300 amps, because that limit is set by the terminal and the plate group rather than by capacity.
- No 30 second rating is published - CSB prints a dash in that row for every part in the HR range, so a worksheet with a 30 second column has to fall back on the 5 minute figure.
Technical Specifications
| CSB HR12120WFR Specifications | |
|---|---|
| Part Number | HR12120WFR (also written HR 12120WFR, HR12120W and hr12120wfr; the FR denotes the flame retardant case, which the CSB price list marks standard on this part) |
| Series | HR, High Rate, 12 volt top terminal |
| Battery Type | AGM, valve regulated lead acid (VRLA), pure lead construction |
| Nominal Voltage | 12V |
| Watts Per Cell, 15 Minutes | 123 W to 1.67 VPC at 25°C (738 W per block) |
| Watts Per Cell, 5 Minutes | 232.17 W to 1.67 VPC at 25°C (1,393 W per block) |
| Watts Per Cell, 30 Seconds | Not published by CSB for the HR range |
| Capacity | 30 Ah at the 20 hour rate (CSB price list) |
| Discharge Current, 15 Minutes | 67.0 A to 1.67 VPC at 25°C |
| Discharge Current, 5 Minutes | 124 A to 1.67 VPC at 25°C |
| Maximum Charge Current | 12 A |
| Maximum Discharge Current | 225 A |
| Short Circuit Current | 928 A |
| Internal Resistance | 8.2 milliohms |
| Terminal Type | I1 recessed threaded lead alloy insert to accept an M5 bolt |
| Terminal Torque | 26.4 ± 5.3 lbf-in (3.0 ± 0.6 N·m) |
| Length | 6.54 inches (166 mm) |
| Width | 4.92 inches (125 mm) |
| Height | 6.89 inches (175 mm) |
| Weight | 20.48 lbs (10.2 kg) |
| BCI Group Size | M26 (CSB price list) |
| Float Charging Voltage | 13.5 to 13.8 VDC per battery at 25°C (77°F) |
| Equalization Charging Voltage | 14.4 to 15.0 VDC per battery at 25°C (77°F) |
| Operating Temperature | Nominal 25°C (77°F); discharge -15°C to 50°C (5°F to 122°F); charge and storage -15°C to 40°C (5°F to 104°F) |
| Self Discharge | Less than 10 percent after 90 days at 25°C, storable up to 6 months at that temperature; a full recharge is required before the block goes into service |
| Container Material | ABS (UL 94-HB) on the base part; the flame retardant 94-V0 case is what the FR build supplies, and the CSB price list marks it standard on this part number |
| Standards | IEC 61056-1/2:2012; UL1973 Listed (MH66728); UL1989 Recognized (MH14533); TUV NORD to ISO 9001:2015 |
| Design Life | Up to 5 years in standby service at 25°C; 3 to 5 years on the Eurobat 20°C basis, standard commercial |
| Warranty | 1 year (CSB, HR High Rate series) |
| Country of Origin | Vietnam |
Where This Battery Is Used
- Larger rack and tower UPS cabinets - units past the point where a 9 Ah brick will do, sized on the 15 minute column to cover a transfer to generator.
- Telecom and network closet backup - small strings on a threaded insert rather than a Faston tab, where the connection has to survive years of thermal cycling.
- Medical and imaging carts - equipment that pulls hard for a short window and is judged on what the bank delivers in the first fifteen minutes.
Ordering and Freight
Frequently Asked Questions
Why does the smaller HR1290WFR carry a higher discharge current limit?
Because maximum discharge current is set by the terminal and the plate group, not by how much energy the block holds. CSB rates the HR1290WFR at 300 amps and this larger part at 225. The figures that do scale with size are the ones that describe sustained output: 123 watts per cell against 90.0, 928 amps of short circuit current against 836, and 8.2 milliohms of internal resistance against 9.9. Size a string on the watts column and check the discharge limit separately against your worst case inrush.
What does the 120 in the part number stand for?
A nominal watts-per-cell figure at the 15 minute rate. CSB's datasheet measures 123 watts per cell to 1.67 volts per cell at 25°C, so the label sits 2.50 percent under the block. That pattern holds across the whole HR range and it never runs the other way: the 1221W measures 25.0 against a 21 label, the 1224W measures 27.0 against 24, the 1251W measures 53.3 against 51, and the 1290W lands exactly on 90.0. Size from the datasheet column and the badge will not flatter the battery.
Can this replace a flooded or a general purpose block of the same amp hour rating?
Amp hours alone will mislead you here. A 30 Ah general purpose AGM is built to hand back its capacity over hours, while this plate design is built to hand back 738 watts in fifteen minutes and then sit on float for years. Swapping a high rate block in where a general purpose one sits costs nothing in performance. Going the other direction shortens the runtime you get at UPS discharge rates, often by a wide margin. Send the load and the transfer window with your quote request and a specialist will confirm the substitution in writing.
Is the flame retardant case standard on this part?
Yes on this one. CSB's datasheet describes the base container as ABS to UL 94-HB with the 94-V0 flame retardant version available on request, while the CSB price list lists this part as HR 12120WFR and marks the FR case standard. That is not true everywhere in the range; the HR1224W, for instance, carries FR as a surcharged option. Where a submittal has to cite the container rating, ask a specialist to confirm it against the build in writing rather than quoting the base datasheet line.
Send the transfer window you have to cover, the tray dimensions and the part number running today. A specialist works the string against the 15 minute column and quotes it with lead time in writing.