Voltage: 12
Capacity: 100 Ah (8-hour rate to 1.75 VPC at 25C)
Chemistry: AGM VRLA, pure lead construction
Terminal: Front terminal, I2 insert, M6 bolt, 44.9 in-lbs
Features: Telecom
Minimum Order Quantity: 4 Batteries
Dimensions: 20.16 x 4.44 x 10.11 in
TPL121000 12V 100AH Telecom Battery High Output Front Terminal CSB

TPL121000 12V 100AH Telecom Battery High Output Front Terminal CSB

$314.95
Adding to cart… The item has been added

CSB TPL121000 Battery - 12V 100Ah Front Terminal Telecom

The TPL121000FR is a 12V 100Ah front-terminal telecom cell built on pure lead for a twelve-year float life. Front terminals mean a technician torques the connection from the aisle rather than pulling the shelf, which is the whole reason front-access batteries exist in a 19-inch rack. CSB rates it at 100Ah at the 8-hour rate to 1.75 VPC, and it will deliver 800 amps on a short, hard demand.

Warranty and Design Life

CSB warrants the TPL series for 3 years. Design life is a separate figure: up to 12 years in standby service at 25°C. Country of origin is Taiwan. Terms are confirmed in writing with your quote.

Built for Float, Not for Cycling

Pure lead construction
Grid corrosion is what ends a standby battery. Pure lead with CSB's proprietary elements corrodes slower than lead-calcium, which is how the cell reaches twelve years on float.
3.7 milliohm internal resistance
Low impedance means less voltage sag in the first minutes of a discharge, and it is the number your IEEE 1188 ohmic trend gets baselined against.
Front terminals, M6
I2 threaded lead-alloy terminals taking an M6 bolt, torqued to 44.9 in-lbs. Service the string from the front of the rack instead of pulling shelves.
  • 800 A maximum discharge current - the cell holds voltage through a hard demand rather than collapsing into a low-voltage disconnect.
  • UL 1973 listed (MH66728) and UL 1989 recognized (MH14533), built to IEC 60896-21/22:2004, TUV NORD certified to ISO 9001:2015.
  • Maintenance-free AGM with up to 99% gas recombination and a flame-retardant UL 94 V-0 container.

Technical Specifications

CSB TPL121000FR Specifications
Part Number TPL121000FR (also written TPL121000, TPL 121000; the FR denotes the 19-inch front-terminal case). A confirmed cross for the GNB Marathon M12V105FT.
Battery Type AGM, valve regulated lead acid (VRLA), pure lead construction
Nominal Voltage 12V
Nominal Capacity 100Ah at the 8-hour rate to 1.75 VPC at 25°C
Also Rated 107Ah at the 20-hour rate to 1.75 VPC; 96.8Ah at the 8-hour rate to 1.80 VPC
Max Discharge Current 800 A
Max Charge Current 30 A
Short Circuit Current 2,216 A
Internal Resistance Approximately 3.70 milliohms
Terminal Type Front terminal, I2 threaded lead-alloy insert accepting an M6 bolt
Terminal Torque 44.9 plus or minus 9.0 in-lbs (5.1 plus or minus 1.0 Nm)
Length 20.16 inches (511.6 mm)
Width 4.44 inches (110.0 mm)
Height 10.11 inches (255.5 mm)
Weight 84.41 lbs (38.30 kg)
Float Charging Voltage 13.5 to 13.8 Vdc per battery at 25°C
Equalize Charging Voltage 14.4 to 15.0 Vdc per battery at 25°C
Operating Temperature Discharge -15°C to 50°C (5°F to 122°F); charge and storage -15°C to 40°C
Container Flame-retardant ABS, UL 94 V-0
Certification UL 1973 listed (MH66728), UL 1989 recognized (MH14533), IEC 60896-21/22:2004
Design Life Up to 12 years standby at 25°C; Eurobat (20°C) greater than 12 years, very long life
Warranty 3 years (CSB, Float Service class)
Country of Origin Taiwan
Minimum Order 4 units

Where This Battery Is Used

  • Central offices and cell sites - the -48V plant string that carries the site until the generator picks up.
  • 19-inch telecom racks and cabinets - where front access is the difference between a ten-minute service call and pulling the shelf.
  • Cable and broadband plant - node and hub cabinets where a truck roll costs more than the battery.
  • Fiber nodes and remote terminals - unmanned sites on a scheduled maintenance visit.
  • Small data center and edge deployments - float service where a twelve-year life beats a three-year swap cycle on total cost.

Ordering and Freight

Minimum order is 4 units. At 84.4 lbs apiece these ship freight pre-paid by LTL to a commercial address; a residential or limited-access delivery adds $100, which is the liftgate and access charge the carrier bills us. Send the quantity, your delivery ZIP and your requested-by date, and a specialist returns a written quote with volume pricing in 24 to 48 hours. If you are matching an existing rack, send a photo of the label and we will confirm the exact case variant before anything ships.

Frequently Asked Questions

What is the difference between the TPL121000FR and the TPL121000TFR?

The case, not the capacity. Both are rated 100Ah at the 8-hour rate. The FR is the 19-inch case sold on this page: 20.16 by 4.44 by 10.11 inches, 84.4 lbs. The TFR is the tall case: 15.35 by 4.13 by 11.02 inches, 76.7 lbs. Nearly five inches shorter front-to-back and about an inch taller. Compare the two on a capacity spec sheet and they look interchangeable; put the wrong one in a fixed rack and it does not fit.

Is it 100Ah or 107Ah?

Both, at different rates. 100Ah at the 8-hour rate to 1.75 VPC is the nameplate and the figure to size against for telecom float service. At the 20-hour rate the same battery gives 107Ah, and at the 8-hour rate to a 1.80 VPC end point it gives 96.8Ah. None of these is wrong; they are three measurements of one battery. Match whichever basis your plant documentation uses.

How is a 12-year design life different from the warranty?

Design life is CSB's engineering estimate of how long the cell can serve under ideal float at 25°C. The warranty is the three-year period CSB will replace a failed unit. The gap between the two is normal across the industry and it is not a catch. Design life is an engineering estimate; the warranty is what CSB will replace.

What torque do the terminals take?

M6 bolts into I2 threaded lead-alloy inserts at 44.9 in-lbs (5.1 Nm), with a tolerance of plus or minus 9 in-lbs. That is much lower than the 110 in-lbs a 1/4-20 top post takes, and over-torquing a lead-alloy insert strips it. Use a torque wrench set to that value.

Does temperature affect the twelve-year life?

Substantially. The 12-year figure is at 25°C (77°F), and the rule of thumb across VRLA chemistry is that life roughly halves for every 8 to 10°C of sustained elevation. A cabinet running at 35°C is not a twelve-year installation. If you know a site runs warm, tell us and we will talk about whether a high-temperature line is the better buy.

How do I confirm this is the right battery before ordering?

Send a photo of the label on the unit you are replacing plus the tray dimensions. Voltage, capacity basis, terminal type and footprint are the four that have to match, and FR against TFR is the one most often missed. We would rather talk you out of the wrong battery than process the return.

Get the TPL121000FR priced for your site

Send the quantity, your delivery ZIP and your requested-by date. A specialist confirms availability, the case variant, volume pricing and freight in writing, with no obligation to buy.

Call 1-877-775-4381  ·  battery specialists, not a call center

WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov (State of California only).

Customer Reviews

Customers Also Viewed