C&D UPS12-1000MRF Battery
C&D UPS12-1000MRF Battery
C&D Dynasty UPS12-1000MRF Battery - 12V 254 Ah High Rate Max Front Access AGM
Warranty
The Largest Block in the Line
- Front terminal, M8 insert at 160 in-lbs - 18 N-m, against 5,540 amps short-circuit current at 0.1 second and 0.0023 ohms reference impedance at 60 Hz.
- Recommended maximum charging current - C20 divided by 5 at the 20-hour rate, which comes to 50.8 amps for this block.
- UL94-V2 flame retardant case and cover - thermally welded together, with a patented UL-recognized flame-arresting vent in each of the six cells.
- Full compliance set - UL1778, UL 924, UL 1989 and UL 94 V-2, plus BS6290-4 and IEC-896-2, on a UL-recognized component.
- Unrestricted for transport - non-hazardous under DOT-CFR Title 49 parts 171-189 and IMDG Amendment 27, and cleared for air under IATA and ICAO Special Provisions A67.
Technical Specifications
| C&D UPS12-1000MRF Specifications | |
|---|---|
| Part Number | UPS12-1000MRF (also searched as UPS12 1000MRF, UPS121000MRF; the F denotes the front-access case; sold under the C&D Dynasty brand) |
| Series | UPS High Rate Max Front Access (MRF), retired by C&D, replaced by UPS12-1005PLPF |
| Battery Type | AGM, valve regulated lead acid (VRLA), high rate, front terminal |
| Nominal Voltage | 12V (6 cells per unit) |
| Nominal Capacity | 254 Ah at the 20-hour rate to 1.75 VPC at 25°C (77°F) |
| Watts Per Cell | 1,000 W per cell at the 15-minute rate to 1.67 VPC at 77°F |
| Constant Power to 1.75 VPC | 1,379.8 W/cell at 5 min, 1,098.4 at 10 min, 907.8 at 15 min, 763.7 at 20 min, 589.7 at 30 min, 345.3 at 60 min, 250.1 at 90 min |
| Constant Power to 1.67 VPC | 1,520 W/cell at 5 min, 1,210 at 10 min, 1,000 at 15 min, 823.7 at 20 min, 616.2 at 30 min, 356.9 at 60 min, 256.7 at 90 min |
| Terminal Type | Front terminal, threaded insert, M8 |
| Terminal Torque | 160 in-lbs (18 N-m) |
| Length | 22.01 inches (559 mm) |
| Width | 6.06 inches (154 mm) |
| Height | 12.68 inches (322 mm), case top and over terminals |
| Weight | 187.9 lbs (85.2 kg) |
| Short Circuit Current | 5,540 A at 0.1 second |
| Impedance | 0.0023 ohms at 60 Hz (reference figure; C&D recommends individual baselines) |
| Design Life | 10 year design life at 25°C (C&D) |
| Warranty | 3 years at 25°C (77°F) (C&D Form 41-9027, UPS High Rate Max series) |
| Minimum Order | 4 units |
Where This Battery Is Used
- Large UPS rooms in data centers - the highest kilowatt rating in the line, on a case maintained from the front.
- Power generation plant backup - control and tripping power in rooms built for cabinet systems, not for open racks.
- Financial and trading floor plant - sites where the ride-through is short, the load is large, and the rear of the cabinet is inaccessible.
Ordering and Freight
Frequently Asked Questions
How does a 187.9 lb block get onto the shelf?
With lifting handles and two people, or a battery lift. C&D's installation guide lists battery lifting equipment and a fork lift for the pallets among the required tools, and notes that individual blocks in this family run from 25 to 180 pounds; the 1000MRF sits just above that stated range at 187.9 lbs, or 85.2 kg. Check the shelf load rating and the freight elevator capacity before the pallet arrives, and load the lowest tiers first for rack stability.
Why is the UPS12-1000MRF wider than the other front-access blocks?
C&D publishes the dimensions and not the reason for them. The 615MRF and the 700MRF are both 125 mm wide, or 4.92 inches; the 1000MRF is 154 mm, or 6.06 inches. Depth stays at 559 mm and height at 322 mm, within a tenth of a millimeter of the 700MRF. So a tier upgraded from 700MRF to 1000MRF keeps its depth and height but gains 1.14 inches of width per block, which is 4.56 inches across a row of four.
What does the UPS12-1000MRF hold for a full hour?
345.3 watts per cell to 1.75 volts per cell, or 356.9 to 1.67, at 77°F. That is 2,072 watts per block for sixty minutes at the 1.75 end point. At ninety minutes the figure drops to 250.1. C&D publishes four end points and ten runtimes for this model, so a plant sized to an unusual combination can be read straight off the table.
What cable size does a UPS12-1000MRF string need?
It depends on the load, and C&D's guide gives the bands: AWG #6 up to 90 amperes, #2 up to 150, #1/0 up to 250, #4/0 up to 400, and two runs of #2/0 up to 600. Intertier, interrow and interrack cables should be at least the same size as the interunit connectors. Size against the discharge current the UPS draws in service. The 5,540 amp figure is the bolted-fault number used to rate the protective device; conductor sizing uses the load current instead.
Send the quantity, your delivery ZIP and your requested-by date. A specialist confirms availability, the warranty term, volume pricing and freight in writing, with no obligation to buy.