Free Shipping
Orders $75 & Up
-
30-day Money Back
Guarantee*
-
100% Secure Online Shopping
SSL - Verified Merchant
NorthStar NSB210FT RED Pure Lead - Long Life Battery
NorthStar NSB210FT RED Pure Lead - Long Life Battery
NorthStar NSB210FT RED Battery - 12V 204Ah Pure Lead AGM, Front Terminal
Warranty
Why the RED Build Exists
Technical Specifications
| Nominal Voltage | 12V (6 cells) |
| Capacity, 8-Hour Rate | 204 Ah to 1.75 VPC at 77°F (25°C) |
| Capacity, 10-Hour Rate | 204 Ah to 1.80 VPC at 68°F (20°C) |
| Chemistry | Thin plate pure lead AGM (VRLA), 99.9% pure lead |
| Internal Resistance | 3.3 milliohms |
| Short Circuit Current | 3,850 A |
| Float Voltage | 2.29 VPC at 68°F (20°C) / 2.27 VPC at 77°F (25°C) |
| Terminal Type | Front terminal, male M6 threaded post, three-stage design, torque 9.0 Nm (80 in-lbs) |
| Length | 22.0 inches |
| Width | 4.9 inches |
| Height | 13.02 inches |
| Weight | 139 lbs (63 kg) |
| Operating Temperature | -40°F to 149°F (-40°C to +65°C) |
| Shelf Life | Up to 24 months |
| Container | UL94 V-0 rated flame retardant, highly resistant to shock, vibration and elevated operating temperatures |
| Transport | Approved as non-hazardous cargo for ground, sea and air |
| Standards | Telcordia SR4228, IEC 60896; Bellcore GR-63-Core; UL approved and UN2800 certified |
| Monitoring | Compatible with the optional EnVision Connect system monitor |
| Design Life | 15+ years at 68°F (20°C); EUROBAT Very Long Life (12+ years) |
| Warranty | 3 years (EnerSys) |
| Specification Source | NorthStar NSB RED range summary, AMER-EN-RS-NSB-RED-0625 (EnerSys, 2025), read first-hand; operating range per the NorthStar per-model data sheet, which governs for this line |
Where This Battery Is Used
- Telecom backup, inside and outside plant - -48 volt strings on 19 and 23-inch shelves, where the front-terminal format puts every connection on the aisle side.
- Cable TV and broadband plant - powering nodes and headend reserves that float for years between events.
- Emergency lighting and life safety - installations where the 15-year design life is written into the specification.
- Railway, oil and gas - remote standby on grids that cannot be relied on, which is the condition the RED line was drawn for.
Ordering and Freight
Frequently Asked Questions
Why does the NSB210FT RED quote an 8-hour rate?
Because the 2025 RED range summary rates the top block at the 8-hour rate to 1.75 VPC at 77°F, which gives 204 Ah. The spec table also carries the 10-hour figure, 204 Ah to 1.80 VPC at 68°F, so it can be set beside the 155FT and 170FT, which are rated at the 10-hour rate. Compare blocks at the same rate, end voltage and temperature, or the capacity figures will not line up.
How do RED, HT RED and BLUE+ differ?
By duty and by cabinet temperature. RED is the long-float-life standby build: 15+ year design life, -40°F to 149°F operating range, and a three-year EnerSys warranty. HT RED shares that range and adds sustained operation at 104°F as a published characteristic, and EnerSys warrants it for four years. BLUE+ is the cycling build, rated 2050 cycles at 50% depth of discharge with a 12+ year design life, and its warranty term is confirmed in writing with your quote. Match the build to how the site treats the battery and to how hot the cabinet gets, then size the capacity.
Does the NSB210FT RED ship as hazardous cargo?
No. The block is a sealed, non-spillable VRLA design certified under UN2800, the classification that lets it travel as non-hazardous cargo by ground, sea and air with its terminals protected against short circuit. The pallet moves by ordinary LTL. If the blocks are going onward by air to a remote site, tell the specialist so that leg is planned with the order.
Can I add one new block to an aged NSB210FT RED string?
Rarely a good idea. In a series string the weakest block sets the runtime, so a new block put into an aged string ages down to the string rather than lifting it, and the replacement delivers less than its own sheet says. A young string with one early failure is worth a call before anything is bought. If the string is several years old, the honest answer is usually to plan the whole string and keep the good survivors as spares. Send the install date and the last set of float readings and a specialist will tell you which case you are in before anything is ordered.
Send the quantity, your delivery ZIP and the cabinet layout. A specialist confirms the 22.0 by 4.9 inch footprint against the shelf, checks the terminal hardware against your cabling, and quotes the set with lead time and freight in writing.
Call 1-877-775-4381 · battery specialists, not a call centerWARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov (State of California only).