Free Shipping
Orders $75 & Up
-
30-day Money Back
Guarantee*
-
100% Secure Online Shopping
SSL - Verified Merchant
Leoch XP12-400FR High Rate AGM Battery
Leoch XP12-400FR High Rate AGM Battery
Leoch XP12-400FR Battery - 12V 400 W per Cell High Rate AGM, 101.6Ah, M6
Warranty
The Low-Profile Block for Three-Phase UPS
- 391.3 amps for 5 minutes - to 1.67 volts per cell, with 222.6 amps at 15 minutes, 129.4 amps at 30 minutes and 69.5 amps for a full hour.
- 101.6 Ah at the 20-hour rate - to 1.80 volts per cell at 25°C, 5.08 amps for 20 hours, for the rare site that runs it as a long-duration reserve.
- 2,304 amps short-circuit current - at approximately 3.6 milliohms internal resistance, fully charged, for DC-side protection coordination.
- Virgin lead plates, copper alloy inserts - low resistance at the plates and the posts, so the voltage holds under load instead of sagging into the inverter's cutoff.
- 100 percent capacity tested - every XP block is discharge tested and matched on voltage and internal resistance before it leaves the plant.
Technical Specifications
| Leoch XP12-400FR Specifications | |
|---|---|
| Part Number | XP12-400FR (also written XP12-400, XP12 400, xp12-400fr and leoch xp12-400) |
| Series | Leoch XP, ultra high rate AGM for UPS, flame retardant (FR) case build |
| Battery Type | High rate AGM, valve regulated lead acid (VRLA), UPS standby service |
| Nominal Voltage | 12V (6 cells) |
| Nominal Rating, 15 Minutes | 400 W per cell to 1.67 VPC at 25°C (2,400 W per battery) |
| Capacity, 20-Hour Rate | 101.6 Ah to 1.80 VPC at 25°C |
| Discharge Current, 5 Minutes | 391.3 A to 1.67 VPC; 290.9 A to 1.80 VPC |
| Discharge Current, 15 Minutes | 222.6 A to 1.67 VPC; 186.4 A to 1.80 VPC |
| Discharge Current, 30 Minutes | 129.4 A to 1.67 VPC; 114.8 A to 1.80 VPC |
| Discharge Current, 1 Hour | 69.5 A to 1.67 VPC; 61.5 A to 1.80 VPC |
| Discharge Power, 5 Minutes | 731.1 W per cell to 1.67 VPC |
| Discharge Power, 1 Hour | 135.4 W per cell to 1.67 VPC |
| Short Circuit Current | 2,304 A |
| Internal Resistance | Approximately 3.6 milliohms, fully charged, at 25°C |
| Maximum Charge Current | 0.25C (25.4 A) at 25°C |
| Float Charge Voltage | 2.25 to 2.30 V per cell at 25°C (13.5 to 13.8 V per battery) |
| Equalization Charge Voltage | 2.30 to 2.40 V per cell at 25°C |
| Temperature Coefficient | -3 mV per cell per °C on float; -4 mV per cell per °C on equalize |
| Terminal Type | M6 threaded insert (Leoch T8) |
| Length | 325.5 mm (12.8 inches) |
| Width | 170 mm (6.69 inches) |
| Container Height | 213 mm (8.39 inches) |
| Total Height | 216 mm (8.50 inches) |
| Weight | 31.6 kg (69.7 lbs) |
| Operating Temperature | Discharge -15°C to 50°C (5°F to 122°F); charge -20°C to 40°C (-4°F to 104°F); storage -15°C to 40°C (5°F to 104°F) |
| Capacity vs Temperature | 106% at 40°C; 100% at 25°C; 86% at 0°C |
| Self Discharge | 3% per month or less at 25°C |
| Container Material | ABS, flame retardant to UL 94 V-0 (the FR build; UL 94 HB is Leoch's standard case) |
| Standards | IEC 60896-21 and -22, third party tested; UL recognized; CE; IATA approved for air freight; IATF 16949 plants |
| Design Life | 12 years at 25°C on float service (Leoch) |
| Warranty | 36 months in UPS service (Leoch, XP) |
Where This Battery Is Used
- Three-phase UPS battery cabinets - the 20 to 100 kVA data center and hospital systems whose cabinets are shelved for a 12.8 by 6.7 inch block under 8.5 inches tall.
- Generator-backed plants - sites where the string only carries the load until the set is on line, and the 5-minute figure of 391 amps is the one that matters.
- Emergency power supply and switchgear - the DC reserve behind breaker tripping and control power in industrial plants, another entry on Leoch's XP application list.
Ordering and Freight
Frequently Asked Questions
What warranty applies, and is the 12-year figure part of it?
Leoch warrants the XP line for 36 months in UPS service. The 12 years is design life, Leoch's estimate of float service at 25°C from the XP12-400 datasheet, and it carries no replacement commitment. Both figures appear on this page, always labeled, because a listing that runs them together is how a buyer ends up believing in a 12-year warranty. The term is confirmed in writing with your quote.
What does the 400 in XP12-400FR stand for?
Watts per cell over a 15-minute discharge to 1.67 volts per cell at 25°C. Leoch names every XP part by this rating rather than by amp hours because the range exists for UPS duty, and a UPS is sized on power over minutes. Six cells make about 2,400 watts from one block for 15 minutes. The 101.6 Ah figure, at the 20-hour rate, is on the sheet as well, and it is the number to use only if the block is asked to run a long, light load.
XP12-400FR or XP12-490FR: which one?
Measure the shelf pitch first. The XP12-400FR stands 216 mm (8.50 inches) on a 325.5 by 170 mm footprint; the XP12-490FR stands 278 mm (10.9 inches) on 335 by 172 mm, so it needs about 2.5 inches more height and a fraction more length and width. If the cabinet takes the taller block, the step from 400 to 490 watts per cell runs the same load roughly 20 percent longer at 42.6 kg per block rather than 31.6. If the shelves were set for an 8.5 inch battery, the XP12-400FR is the correct answer, and more runtime then comes from adding strings rather than height.
What charger settings does the XP12-400FR want?
Float at 2.25 to 2.30 volts per cell, which is 13.5 to 13.8 volts on the block at 25°C, compensated at -3 millivolts per cell per degree. Equalization, where the charger and the site practice call for it, runs at 2.30 to 2.40 volts per cell at -4 millivolts per cell per degree. Charge current is capped at 0.25C, about 25.4 amps for this 101.6 Ah block. Most three-phase UPS rectifiers sit inside these figures already; the setting to verify is the float voltage, because a charger left at a flooded-cell float will overcharge an AGM string over the years.
Send the UPS model, the shelf pitch, the quantity and your delivery ZIP. A specialist confirms the 8.50 inch height clears, checks the M6 hardware against your interconnects, and quotes the set with lead time and freight in writing.
Call 1-877-775-4381 · battery specialists, not a call centerWARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov (State of California only).