Leoch XP12-210FR High Rate AGM Battery
Leoch XP12-210FR Battery - 12V 210 W per Cell High Rate AGM, 55Ah at 20 Hours, M6
Warranty
55 Ah at 20 Hours, Built for Fifteen Minutes
- 237.5 amps for 5 minutes - to 1.67 volts per cell, with 127.0 amps at 15 minutes, 73.1 amps at 30 minutes and 39.5 amps for a full hour.
- 55 Ah at the 20-hour rate - to 1.80 volts per cell at 25°C, 2.75 amps for 20 hours, for the rare site that runs it as a long-duration reserve.
- Virgin lead plates - from Leoch's XP range summary.
- IATA approved for air freight - per Leoch's XP range summary; ask the specialist if a site needs it flown.
Technical Specifications
| Leoch XP12-210FR Specifications | |
|---|---|
| Part Number | XP12-210FR (also written XP12-210, XP12 210, xp12-210fr and leoch xp12-210) |
| Series | Leoch XP, ultra high rate AGM for UPS, FR (flame retardant) build |
| Battery Type | High rate AGM, valve regulated lead acid (VRLA), UPS standby service |
| Nominal Voltage | 12V (6 cells) |
| Nominal Rating, 15 Minutes | 210 W per cell to 1.67 VPC at 25°C (1,260 W per battery) |
| Capacity, 20-Hour Rate | 55 Ah to 1.80 VPC at 25°C |
| Discharge Current, 5 Minutes | 237.5 A to 1.67 VPC; 175.1 A to 1.80 VPC |
| Discharge Current, 15 Minutes | 127.0 A to 1.67 VPC; 102.4 A to 1.80 VPC |
| Discharge Current, 30 Minutes | 73.1 A to 1.67 VPC; 64.2 A to 1.80 VPC |
| Discharge Current, 1 Hour | 39.5 A to 1.67 VPC; 35.9 A to 1.80 VPC |
| Discharge Power, 5 Minutes | 443.8 W per cell to 1.67 VPC |
| Discharge Power, 1 Hour | 77.1 W per cell to 1.67 VPC |
| Short Circuit Current | 1,262.4 A |
| Internal Resistance | Approximately 5 milliohms, fully charged, at 25°C |
| Maximum Charge Current | 0.25C (13.75 A) at 25°C |
| Float Charge Voltage | 2.25 to 2.30 V per cell at 25°C (13.5 to 13.8 V per battery) |
| Equalization Charge Voltage | 2.30 to 2.40 V per cell at 25°C |
| Temperature Coefficient | -3 mV per cell per °C on float; -4 mV per cell per °C on equalize |
| Terminal Type | M6 (Leoch terminal T6) |
| Length | 229 mm (9.02 inches) |
| Width | 138 mm (5.43 inches) |
| Container Height | 200 mm (7.87 inches) |
| Total Height | 203 mm (7.99 inches) |
| Weight | 17.7 kg (39.0 lbs) |
| Operating Temperature | Discharge -15°C to 50°C (5°F to 122°F); charge -20°C to 40°C (-4°F to 104°F); storage -15°C to 40°C (5°F to 104°F) |
| Capacity vs Temperature | 106% at 40°C; 100% at 25°C; 86% at 0°C |
| Self Discharge | 3% per month or less at 25°C |
| Container Material | ABS, UL 94 HB standard; UL 94 V-0 optional (Leoch datasheet); UL 94 rating confirmed with your quote |
| Standards | IEC 60896-21 and -22, third party tested; UL recognized; CE; IATA approved for air freight; IATF 16949 plants |
| Design Life | 12 years at 25°C (Leoch) |
| Warranty | 36 months in UPS service (Leoch, XP) |
Where This Battery Is Used
- UPS battery strings - first on Leoch's XP application list, where the 15-minute watts-per-cell rating does the sizing.
- Hospitals and testing laboratories - named on Leoch's XP application list; send the equipment's UPS model with the quote request.
- Telecommunications and data centers - both on Leoch's XP application list.
Ordering and Freight
Frequently Asked Questions
What does the 210 in XP12-210FR stand for?
It is Leoch's nominal rating for this block, in watts per cell, for a 15-minute discharge to 1.67 volts per cell at 25°C, and it is the number in the part name. Sizing a runtime uses the constant power table, covered in the next answer.
How do I turn the watts per cell into a runtime for my UPS?
Take the UPS's DC bus load in watts, or the AC load divided by the inverter efficiency, and divide it by the number of blocks in the string times six cells. That gives the watts per cell each block must supply. Read down the constant power table to find where that figure sits: at 15 minutes the table gives 240.8 watts per cell, at 30 minutes 140.6, at one hour 77.1. If the load per cell is above the 15-minute figure, the runtime is shorter than 15 minutes and the 5- and 10-minute rows apply. A specialist will run the calculation from the UPS model if you would rather not.
Should I move up to the XP12-300FR instead?
Only if the tray takes it. The XP12-300FR is 10.24 by 6.61 inches and 8.31 inches tall at 53.4 lbs, a wider and longer block, so it will not fit a tray drawn for the XP12-210FR's 9.02 by 5.43 inch footprint. If the tray does fit the larger block, Leoch rates it at 300 watts per cell at 15 minutes against 210 for this block. If it does not, extra runtime comes from adding strings in parallel rather than a bigger block, and the quote can price either way.
Send the UPS model, the quantity and your delivery ZIP. A specialist confirms the 9.02 by 5.43 inch footprint against the tray, checks the M6 hardware, and quotes the set with lead time and freight in writing.
Call 1-877-775-4381 · battery specialists, not a call centerWARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov (State of California only).