Free Shipping
Orders $75 & Up
-
30-day Money Back
Guarantee*
-
100% Secure Online Shopping
SSL - Verified Merchant
EnerSys DataSafe 12HX330FR Battery | 12V 336WPC AGM | Telecom
EnerSys DataSafe 12HX330FR Battery - 12V 83Ah 336 WPC UPS AGM
Warranty
Built for the Fifteen-Minute Job
- Sealed AGM VRLA, non-spillable - recombination design with self-resealing flame-arresting vents, no watering.
- UL File MH12544 and UL94 case - the flame-retardant container built to meet UL 1778.
- Compression grommet terminal seals - the long-life sealing EnerSys fits to the 205-through-540 case sizes.
- Six-month storage at 77°F - before a freshening charge is required; heat shortens the interval.
Technical Specifications
| EnerSys DataSafe 12HX330-FR Specifications | |
|---|---|
| Part Number | 12HX330-FR (listed here as 12HX330FR; also searched as 12HX330, HX330) |
| Battery Type | AGM VRLA, top terminal, UPS float service |
| Nominal Voltage | 12V |
| Capacity, 8-hour rate | 83 Ah to 1.75 VPC at 77°F |
| Rated Power, 15-minute rate | 336 watts per cell to 1.67 VPC at 77°F |
| Power, 5-minute rate | 590 watts per cell to 1.75 VPC |
| Short Circuit Current | 3,700 A |
| Internal Resistance | 0.0034 ohm (reference value) |
| Terminal Type | M6 brass threaded receptacle, torque 60 in-lbs (6.8 N-m) ±5% |
| Length | 11.8 inches (300 mm) |
| Width | 6.8 inches (173 mm) |
| Height, including terminal | 8.4 inches (213 mm) |
| Weight | 71 lbs (32.2 kg) |
| Operating Temperature | -22°F to +122°F (-30°C to +50°C) |
| Float Charging Voltage | 2.25 to 2.28 volts per cell at 77°F |
| Storage | Up to 6 months at 77°F before a freshening charge is required |
| Listings | UL File MH12544; UL94 flame-retardant case |
| Design Life | 10 years in standby service (EnerSys estimate) |
| Warranty | 4 years in float service (EnerSys) |
Where This Battery Is Used
- Data room UPS strings - the holdover between mains failure and generator start.
- High-rate DC standby - plants sized in watts per cell rather than amp hours.
- Certified seismic cabinets - the HX rack and cabinet program covers this model.
Ordering and Freight
Frequently Asked Questions
Is the 12HX330 right for a telecom plant, or just UPS work?
It is a UPS battery first. EnerSys optimizes the HX line for high power over short windows, the 5-to-30 minute discharges a UPS rides out, where its watts-per-cell ratings shine. A telecom plant that needs hours of reserve is better served per dollar by a long-duration line such as PowerSafe SBS, and we will say so on the quote. Where the same site runs both duties, the two lines coexist happily on separate strings.
What is UL File MH12544?
It is the UL recognition file covering the large-case DataSafe HX models, 12HX205 through 12HX540, and the number a facility auditor can look up to confirm the listing. Pair it with the UL94 flame-retardant case, built to meet UL 1778 for UPS equipment, and the paperwork side of a data room install is covered. The smaller HX models carry their own file, MH16464, so quote the model when an auditor asks.
How tight do the terminal bolts go?
60 inch-pounds, plus or minus five percent, into the M6 brass receptacles, the figure EnerSys publishes for the large-case HX models. Use a torque wrench rather than feel: brass inserts strip when overtightened and a loose joint heats under load, and both failures show up at the worst moment, mid-discharge. Recheck torque at commissioning and on the maintenance interval your site standard sets.
Send the quantity, your delivery ZIP and your requested-by date. A specialist confirms availability, the warranty term, volume pricing and freight in writing, with no obligation to buy.
Call 1-877-775-4381 · battery specialists, not a call centerWARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov (State of California only).