EnerSys DataSafe 12HX300-FR Battery | 12V 284WPC AGM | Telecom
EnerSys DataSafe 12HX300-FR Battery | 12V 284WPC AGM | Telecom
EnerSys DataSafe 12HX300-FR Battery - 12V 71Ah 284 WPC UPS AGM
Warranty
The Entry to the Big-Case HX Range
- Sealed AGM VRLA, non-spillable - gas recombination construction, approved for transport as non-hazardous per IATA Special Provision A67 and 49 CFR.
- UL File MH12544 - with a UL94 flame-retardant container built to meet UL 1778.
- -22°F operating floor - the wider window the 12HX205-FR through 12HX540-FR band carries.
- Zone 4 cabinet program - EnerSys certifies HX battery cabinets to UBC Zone 4 and IBC 2012 seismic criteria.
Technical Specifications
| EnerSys DataSafe 12HX300-FR Specifications | |
|---|---|
| Part Number | 12HX300-FR (also searched as 12HX300, HX300, 12 HX 300) |
| Battery Type | AGM VRLA, top terminal, UPS float service |
| Nominal Voltage | 12V |
| Capacity, 8-hour rate | 71 Ah to 1.75 VPC at 77°F |
| Rated Power, 15-minute rate | 284 watts per cell to 1.67 VPC at 77°F |
| Power, 5-minute rate | 513 watts per cell to 1.75 VPC |
| Short Circuit Current | 3,175 A |
| Internal Resistance | 0.0039 ohm (reference value) |
| Terminal Type | M6 brass threaded receptacle, torque 60 in-lbs (6.8 N-m) ±5% |
| Length | 10.2 inches (259 mm) |
| Width | 6.9 inches (175 mm) |
| Height, including terminal | 8.2 inches (208 mm) |
| Weight | 60 lbs (27.2 kg) |
| Operating Temperature | -22°F to +122°F (-30°C to +50°C) |
| Float Charging Voltage | 2.25 to 2.28 volts per cell at 77°F |
| Storage | Up to 6 months at 77°F before a freshening charge is required |
| Listings | UL File MH12544; UL94 flame-retardant case |
| Design Life | 10 years in standby service (EnerSys estimate) |
| Warranty | 4 years in float service (EnerSys) |
Where This Battery Is Used
- Three-phase UPS strings - the 15-minute class reserve behind server rooms and critical loads.
- Compact high-power plants - installs sized in watts per cell where floor space is tight.
- Seismic cabinet installs - sites specifying the certified HX cabinet and rack program.
Ordering and Freight
Frequently Asked Questions
Is the 12HX300 a 70 Ah or 71 Ah battery?
EnerSys's current range summary publishes 71 Ah at the 8-hour rate to 1.75 volts per cell; size from that figure. Older literature carried a 70 Ah rounding, and it survives in some listings, this page's address among them. One amp hour changes no sizing decision in this class, and UPS work sizes from the 284 watts per cell at the 15-minute rate in any case.
Can I step up to the 12HX330 later for more runtime?
Only as a full string swap, and only if the tray allows it: the 330 runs 11.8 inches long against this model's 10.2, an inch and a half a packed shelf may not have. It buys 83 Ah and 336 watts per cell against 71 and 284. If growth is on the roadmap, measure for the larger case now and quote both models; carrying the extra length from day one costs less than rebuilding shelves later.
What float voltage does an HX string want?
EnerSys publishes 2.25 to 2.28 volts per cell at 77°F, which is 13.5 to 13.68 per 12V bloc, and the HX design also accepts recharge at high current rates after a discharge. Confirm the UPS's float setpoint lands in that window at commissioning and temperature-compensate where the equipment supports it. A string floated outside the published band ages faster than any spec sheet predicts.
Send the quantity, your delivery ZIP and your requested-by date. A specialist confirms availability, the warranty term, volume pricing and freight in writing, with no obligation to buy.