CSB XPL6700 12V AGM High-Rate Deep Cycle Battery for Standby Power Applications
CSB XPL6700 12V AGM High-Rate Deep Cycle Battery for Standby Power Applications
CSB XPL6700 Battery - 12V 140 Ah Extreme Power Long Life AGM
Warranty
More Capacity Without More Floor
- Group 31T case - the taller group 31 variant; confirm shelf clearance rather than shelf area, because the floor dimensions are identical to the 5700.
- 55.80 amps maximum charge current - the highest in the top terminal range, which shortens recovery after a deep discharge on a large bank.
- 1,350 amps over 5 seconds - the published peak discharge, which is inrush headroom and not sustainable.
- 2.33 milliohms internal - slightly above the smaller 5700's 2.22, because resistance follows cell geometry rather than capacity.
- Storable to six months at 25°C - with self discharge under 10 percent across 90 days, and the recharge date brought forward in a warm stockroom.
Technical Specifications
| CSB XPL6700 Specifications | |
|---|---|
| Part Number | XPL6700 (also searched as XPL 6700, XPL6700FR and xpl6700; CSB prints the flame retardant build as XPL 6700FR) |
| Series | XPL, Extreme Power long life, top terminal |
| Battery Type | AGM, valve regulated lead acid (VRLA), pure lead construction |
| Nominal Voltage | 12V |
| Nominal Capacity | 140 Ah at the 20-hour rate to 1.75 VPC at 25°C (77°F), per the CSB price list; the per-part datasheet rates this series in watts only |
| Watts Per Cell, 15 Minutes | 651 W to 1.67 VPC at 25°C |
| Watts Per Cell, 5 Minutes | 1,055 W to 1.67 VPC at 25°C |
| Watts Per Cell, 30 Seconds | 1,467 W to 1.67 VPC at 25°C |
| Maximum Charge Current | 55.80 A |
| Maximum Discharge Current | 1350 A (5 second rate) |
| Short Circuit Current | 4,018 A |
| Internal Resistance | Approximately 2.33 milliohms |
| Terminal Type | I2 threaded lead alloy insert, accepts an M6 bolt |
| Terminal Torque | 44.9 ±9.0 lbf-in (51.7 ±10.3 kgf-cm, 5.10 ±1.0 N-m) |
| Length | 13.50 inches (343.0 mm) |
| Width | 6.69 inches (170.0 mm) |
| Height | 10.85 inches (275.7 mm) |
| Weight | 105.57 lbs (47.90 kg) |
| BCI Group Size | 31T |
| Float Charging Voltage | 13.5 to 13.8 VDC per battery at 25°C (77°F) |
| Equalization Charging Voltage | 14.4 to 15.0 VDC per battery at 25°C (77°F) |
| Operating Temperature | Nominal 25°C (77°F); discharge -15°C to 50°C (5°F to 122°F); charge and storage -15°C to 40°C (5°F to 104°F) |
| Self Discharge | Less than 10 percent after 90 days at 25°C; storable to six months before a full recharge |
| Container Material | Polypropylene (UL 94-HB); flame retardant 94-V0 available on request |
| Standards | IEC 60896-21/22:2004; UL1973 Listed (MH66728); UL1989 Recognized (MH14533); TUV NORD to ISO 9001:2015 |
| Design Life | Up to 10 years in standby service at 25°C; greater than 12 years on the Eurobat 20°C basis |
| Warranty | 5 years (CSB, XPL Extreme Power range) |
| Country of Origin | Taiwan |
Where This Battery Is Used
- Large UPS and data center plant - where the bank is sized in hundreds of kilowatts and floor area is already committed.
- Utility and substation standby - long float intervals with replacement set by impedance trend rather than by failure.
- Capacity upgrades in a fixed footprint - where the room cannot grow but the racking has vertical clearance to spare.
Ordering and Freight
Frequently Asked Questions
Can I swap a 5700 string for 6700s in place?
The floor area is identical at 13.50 by 6.69 inches, so the shelf footprint works. Height is what stops it: the 6700 stands 10.85 inches against the 5700's 8.53, so you need 2.32 inches more clearance per shelf plus room for the terminal hardware. Weight per shelf also rises by 24.24 pounds a block. Send the rack drawing and we will check both before quoting.
Why does the 6700 show higher resistance than the 5700?
Internal resistance tracks cell geometry and plate construction, not capacity, so it does not fall in a straight line as the blocks get bigger. CSB publishes 2.33 milliohms here and 2.22 for the 5700. Use each block's own published figure when you model string voltage, rather than interpolating across the range, and take your own commissioning readings once the bank is in.
Is 140 Ah the number I should be specifying from?
Only as a cross-check. A UPS discharges hard for minutes, and capacity is measured drawing gently for 20 hours, so the two describe different behavior. The 651 watts per cell at 15 minutes governs the ride-through you will get. Use the capacity figure to compare this block against a competitor's datasheet, and the watts figure to size the string.
What does the 30 second rating tell me?
It covers the first instant of a transfer, where motor inrush and power supply charging can push the draw well above the steady load. CSB publishes 1,467 watts per cell at 30 seconds for this block. On loads with a heavy inrush component it can be the figure that decides the size, even when the 15 minute column looks comfortable.
Send the rack clearance you have and the load you need to carry. A specialist confirms the 6700 fits and covers it, or names the alternative, in writing with no obligation.
Call 1-877-775-4381 · battery specialists, not a call centerWARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov (State of California only).