Leoch PLX12-540 Pure Lead High Rate Battery
Leoch PLX12-540 Pure Lead High Rate Battery
Leoch PLX12-540 Battery - 12V 135Ah Pure Lead High Rate AGM, M6
Warranty
Built for the Cabinet Nobody Cools
- 135 Ah at 10 hours - to 1.80 volts per cell at 25°C; the 20-hour row gives 6.79 amps, or about 136 Ah, so the two rates agree.
- 486 amps for 5 minutes - to 1.67 volts per cell, the current a large UPS draws while the generator is still spinning up.
- 310.3 amps for 15 minutes - to 1.67 volts per cell, or 273.5 amps to the gentler 1.75 volt end point most UPS makers specify.
- 105 amps for one hour - to 1.67 volts per cell, for the plant that wants an hour of bridge time rather than fifteen minutes.
- 2,970 amps short circuit, 3.6 milliohms - the pair of figures that go into DC breaker coordination and string fusing.
Technical Specifications
| Leoch PLX12-540 Specifications | |
|---|---|
| Part Number | PLX12-540 (also written PLX12 540, PLX 12-540 and plx12-540) |
| Series | Leoch PLX, pure lead thin plate high rate, top terminal |
| Battery Type | Pure lead thin plate AGM, valve regulated lead acid (VRLA) |
| Nominal Voltage | 12V (6 cells) |
| Nominal Rating, 15 Minutes | 540 W per cell to 1.67 VPC at 25°C (3,240 W per battery); discharge table row reads 560 W per cell |
| Capacity, 10-Hour Rate | 135 Ah to 1.80 VPC at 25°C |
| Discharge Current, 5 Minutes | 486.0 A to 1.67 VPC; 375.8 A to 1.80 VPC |
| Discharge Current, 15 Minutes | 310.3 A to 1.67 VPC; 273.5 A to 1.75 VPC; 246.3 A to 1.80 VPC |
| Discharge Current, 1 Hour | 105.0 A to 1.67 VPC; 96.2 A to 1.80 VPC |
| Discharge Power, 1 Hour | 201.0 W per cell to 1.67 VPC |
| Short Circuit Current | 2,970 A |
| Internal Resistance | Approximately 3.6 milliohms, fully charged, at 25°C |
| Maximum Charge Current | 0.3C (40.5 A) at 25°C |
| Float Charge Voltage | 2.27 ± 0.02 V per cell at 25°C |
| Equalization Charge Voltage | 2.35 to 2.40 V per cell at 25°C |
| Temperature Coefficient | -3 mV per cell per °C on float; -4 mV per cell per °C on equalize |
| Terminal Type | M6 threaded insert (T8); M8 (T11) optional |
| Length | 340.9 mm (13.4 inches) |
| Width | 170 mm (6.69 inches) |
| Container Height | 273.2 mm (10.8 inches) |
| Total Height | 275.7 mm (10.9 inches) |
| Weight | 43.5 kg (95.9 lbs) |
| Operating Temperature | Discharge -40°C to 65°C (-40°F to 149°F); charge -20°C to 54°C (-4°F to 129°F); storage -20°C to 50°C (-4°F to 122°F) |
| Effect of Temperature on Capacity | 103% at 40°C; 100% at 25°C; 86% at 0°C |
| Self Discharge and Storage | Up to 24 months storage at 25°C, shorter when warmer; freshening charge at 2.10 V per cell open circuit or at the storage limit |
| Container Material | PC-ABS, flame retardant to UL 94 V-0, heat sealed and 100% leak tested |
| Standards | IEC 60896; Eurobat "Very Long Life"; CE and UL; IATF 16949, ISO 9001, ISO 14001 and ISO 45001 plants |
| Design Life | 15 years at 25°C on float service (Leoch) |
| Warranty | 60 months, full replacement (Leoch, PLX) |
Where This Battery Is Used
- UPS strings in unconditioned rooms - electrical rooms, mezzanines and container plants where the ambient swings and the battery has to give its 15 minutes anyway.
- Emergency power and lighting plants - central inverter systems for egress lighting and life safety loads, where the discharge is short and the float years are long.
- Test benches and laboratory supplies - equipment that needs several hundred amps on demand without a generator in the building.
Ordering and Freight
Frequently Asked Questions
Does a 15-year design life mean Leoch covers the battery for 15 years?
No. Design life is Leoch's estimate of how long the PLX12-540 will serve on float at 25°C, an engineering figure published on the datasheet. The warranty is 60 months, full replacement, and it is the only period Leoch commits to in writing. The gap is normal for a standby battery of this class. Hold the room near 25°C, float at 2.27 volts per cell, and the design life is achievable; run it hotter and the years come off the design life first. Warranty terms are confirmed in writing with your quote.
Why does the discharge table show 560 watts per cell when the part is rated 540?
The part number carries Leoch's nominal 15-minute rating, 540 watts per cell to 1.67 volts. The constant power discharge table on the same sheet lists 560 watts per cell in the 15-minute column. Datasheet tables are measured values and a rating is a round commitment, so the table sitting above the rating is the direction you want. Size the string on the 540 figure that Leoch stands behind and treat the extra 20 watts per cell as margin. If a UPS manufacturer's runtime table is built on watts per cell at 1.67 volts, the 540 figure drops straight into it.
How do the PLX12-500, PLX12-540 and PLX12-620 differ if the case is the same?
Plate count and rating. All three are 340.9 by 170 mm and 275.7 mm tall with M6 terminals, so they interchange physically. The PLX12-500 gives 500 watts per cell and 125 Ah at 41.7 kg; the PLX12-540 gives 540 watts and 135 Ah at 43.5 kg; the PLX12-620 gives 620 watts and 145 Ah at 44 kg. Weight rises with the amount of lead. Pick by the runtime the UPS needs at full load, and do not mix the three in one string: the lighter block reaches its end voltage first and the string is only as good as that block.
The battery room hits 40°C in summer. Is that inside the ratings?
Inside the discharge and charge windows, yes: Leoch rates discharge from -40°C to 65°C and charging from -20°C to 54°C, and at 40°C the sheet shows 103 percent of rated capacity. Ratings and longevity are different questions. Design life is quoted at 25°C, and heat above that shortens a lead acid battery's float life on every manufacturer's sheet. A charger with temperature compensation at -3 millivolts per cell per degree, as the datasheet specifies, protects the plates from overcharge in a hot room. If the room runs warm year round, tell the specialist; it affects how the replacement interval is planned.
Send the UPS model or the runtime target, the room conditions, the quantity and your delivery ZIP. A specialist confirms whether the PLX12-540 is the right rating for the case, then quotes the set with lead time and freight in writing.