Leoch PLX12-420 Pure Lead High Rate Battery
Leoch PLX12-420 Battery - 12V 100Ah Pure Lead High Rate AGM, M6
Warranty
Short Case, Full Rating
- 420 watts per cell, 15 minutes - to 1.67 volts per cell at 25°C, the figure a UPS runtime table is built on; 394.8 watts to the 1.80 volt end point.
- 236.3 amps for 15 minutes - to 1.67 volts per cell, and 154 amps for 30 minutes, the middle of the discharge curve where most outages end.
- 83.1 amps for one hour - to 1.67 volts per cell, or 156.7 watts per cell over the same hour.
- 100 Ah at 10 hours - to 1.80 volts per cell; the 20-hour row gives 5.28 amps, about 106 Ah, so the block has a little more in it at low rates.
- 2,200 amps short circuit - at approximately 3.5 milliohms fully charged, for DC-side protection coordination.
Technical Specifications
| Leoch PLX12-420 Specifications | |
|---|---|
| Part Number | PLX12-420 (also written PLX12 420, PLX 12-420 and plx12-420) |
| Series | Leoch PLX, pure lead thin plate high rate, top terminal |
| Battery Type | Pure lead thin plate AGM, valve regulated lead acid (VRLA) |
| Nominal Voltage | 12V (6 cells) |
| Nominal Rating, 15 Minutes | 420 W per cell to 1.67 VPC at 25°C (2,520 W per battery) |
| Capacity, 10-Hour Rate | 100 Ah to 1.80 VPC at 25°C |
| Discharge Current, 5 Minutes | 444.6 A to 1.67 VPC; 335.9 A to 1.80 VPC |
| Discharge Current, 15 Minutes | 236.3 A to 1.67 VPC; 208.4 A to 1.80 VPC |
| Discharge Current, 30 Minutes | 154.0 A to 1.67 VPC; 135.9 A to 1.80 VPC |
| Discharge Current, 1 Hour | 83.1 A to 1.67 VPC; 75.1 A to 1.80 VPC |
| Discharge Power, 1 Hour | 156.7 W per cell to 1.67 VPC |
| Short Circuit Current | 2,200 A |
| Internal Resistance | Approximately 3.5 milliohms, fully charged, at 25°C |
| Maximum Charge Current | 0.3C (30 A) at 25°C |
| Float Charge Voltage | 2.27 ± 0.02 V per cell at 25°C |
| Equalization Charge Voltage | 2.35 to 2.40 V per cell at 25°C |
| Temperature Coefficient | -3 mV per cell per °C on float; -4 mV per cell per °C on equalize |
| Terminal Type | M6 threaded insert (T8); M8 (T11) optional |
| Length | 340.9 mm (13.4 inches) |
| Width | 170 mm (6.69 inches) |
| Container Height | 213.2 mm (8.39 inches) |
| Total Height | 215.7 mm (8.49 inches) |
| Weight | 33.5 kg (73.9 lbs) |
| Operating Temperature | Discharge -40°C to 65°C (-40°F to 149°F); charge -20°C to 54°C (-4°F to 129°F); storage -20°C to 50°C (-4°F to 122°F) |
| Self Discharge and Storage | Up to 24 months storage at 25°C, shorter when warmer; freshening charge at 2.10 V per cell open circuit or at the storage limit |
| Container Material | PC-ABS, flame retardant to UL 94 V-0, heat sealed and 100% leak tested |
| Standards | IEC 60896; Eurobat "Very Long Life"; CE and UL; IATF 16949, ISO 9001, ISO 14001 and ISO 45001 plants |
| Design Life | 15 years at 25°C on float service (Leoch) |
| Warranty | 60 months, full replacement (Leoch, PLX) |
Where This Battery Is Used
- UPS cabinets with tight shelf pitch - the internal battery bays and low external cabinets where the 8.49 inch height is the reason this part fits and its taller siblings do not.
- Emergency power supplies - egress and life safety inverters that see a short discharge a few times a year and float the rest of the time.
- Data closets and edge sites - small rooms with one or two strings, where a 74 lb block can be handled by two people without lifting gear.
Ordering and Freight
Frequently Asked Questions
Is the warranty 60 months or 15 years?
60 months. Leoch warrants the PLX12-420 for 60 months with full replacement. The 15 years is the design life Leoch publishes on the datasheet, an estimate of float service at 25°C, and it is not a period during which anyone replaces a failed battery. Both figures appear on this page, always labeled, because a listing that runs them together is how a buyer ends up believing in a 15-year warranty. Terms are confirmed in writing with your quote.
What does the 420 in PLX12-420 stand for?
Watts per cell over a 15-minute discharge to 1.67 volts per cell at 25°C. Leoch names every PLX part by this rating rather than by amp hours, because the range exists for UPS duty and a UPS is sized on power over minutes. A 12 volt battery has six cells, so the PLX12-420 delivers about 2,520 watts for 15 minutes. The amp hour figure, 100 Ah at the 10-hour rate, is on the sheet as well and is the number to use if the block is ever asked to run a long, light load instead.
How does 100 Ah translate into UPS runtime?
Loosely, and the sheet's power table is the better tool. Amp hours are measured over 10 hours at a low current; a UPS pulls its energy in minutes at a high current, and the usable capacity falls as the rate rises. That is why Leoch publishes the constant power table: at 15 minutes the PLX12-420 gives 420 watts per cell, at 30 minutes 283.4, at one hour 156.7. Multiply the watts per cell by six, then by the number of blocks in the string, and compare that against the load in watts at the runtime you need. A specialist will run the string calculation from the UPS model if you would rather not.
Can it replace a PLX12-405 or PLX12-460?
Often, with a check. Leoch's range summary lists the PLX12-405 at 306 by 168 mm and 210 mm total height, the PLX12-420 at 340.9 by 170 mm and 215.7 mm, and the PLX12-460 at 340.9 by 170 mm and 215.7 mm. The PLX12-460 shares this exact case and terminal, so a swap is physical like for like with a 40 watt per cell step down in rating, which a UPS runtime table will show. The PLX12-405 is 35 mm shorter in length and its tray may not accept the longer block. Send the existing part number and a photo of the tray, and the quote will state which swap holds and what the runtime change is.
Send the shelf pitch, the UPS model and the quantity. A specialist confirms the 215.7 mm height clears, checks the terminal hardware against your connectors, and quotes the set with lead time and freight in writing.
Call 1-877-775-4381 · battery specialists, not a call centerWARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov (State of California only).