The 540 in the Large Case
- Sealed AGM VRLA, non-spillable - gas recombination design, safe in offices and equipment rooms, approved for transport as non-hazardous per IATA Special Provision A67 and 49 CFR.
- UL listing, flame-retardant case - UL File MH12544, with a UL94 flame-retardant container built to meet UL 1778.
- Cold-rated to -22°F - the large-case HX models (12HX205-FR through 12HX540-FR) carry a wider operating window than the small ones.
- Seismic rack and cabinet program - EnerSys certifies HX battery cabinets to UBC Zone 4 and IBC 2012, and the 12HX540-FR shares its rack data sheets with the 12HX505-FR.
Technical Specifications
| EnerSys DataSafe 12HX540-FR Specifications | |
|---|---|
| Part Number | 12HX540-FR (listed here as HX540-12FR; also searched as 12HX540, 12 HX 540) |
| Battery Type | AGM VRLA, top terminal, UPS float service |
| Nominal Voltage | 12V |
| Capacity, 8-hour rate | 123 Ah to 1.75 VPC at 77°F |
| Rated Power, 15-minute rate | 540 watts per cell to 1.67 VPC at 77°F |
| Power, 5-minute rate | 835 watts per cell to 1.75 VPC |
| Short Circuit Current | 4,775 A |
| Internal Resistance | 0.0026 ohm (reference value) |
| Terminal Type | M6 brass threaded receptacle, torque 60 in-lbs (6.8 N-m) ±5% |
| Length | 13.3 inches (338 mm) |
| Width | 6.8 inches (173 mm) |
| Height, including terminal | 10.7 inches (272 mm) |
| Weight | 106 lbs (48.1 kg) |
| Operating Temperature | -22°F to +122°F (-30°C to +50°C) |
| Float Charging Voltage | 2.25 to 2.28 volts per cell at 77°F |
| Storage | Up to 6 months at 77°F before a freshening charge is required |
| Listings | UL File MH12544; UL94 flame-retardant case |
| Warranty | 4 years in float service (EnerSys) |
Where This Battery Is Used
- Three-phase UPS strings - the 15-minute class reserve behind data rooms and critical loads.
- High-power, short-duration plants - installs sized in watts per cell rather than amp hours.
- Seismic-rated battery cabinets - Zone 4 certified cabinet installs where the HX program is specified.
Ordering and Freight
Frequently Asked Questions
My records say HX540-12FR. Is that this battery?
Yes. EnerSys's range summary lists the model as 12HX540-FR, and HX540-12FR is the part number our listing carries for it. The flame-retardant case is the standard build for this model. Whichever form your paperwork carries, the battery that ships is the unit on this page: 123 Ah at the 8-hour rate, 540 watts per cell at the 15-minute rate.
When is the 12HX540 worth choosing over the 12HX505?
The two share one case, one terminal layout and one rack program, so the tray never decides between them. The 540 carries 123 Ah against 119 at the 8-hour rate, delivers 540 watts per cell against 506 at the 15-minute rate, and weighs three pounds more. Choose it when the runtime calculation lands close to the 505's limit and you want the margin; when the 505 clears your load comfortably, the smaller unit does the job and costs less.
Can I put new 12HX540s into my existing string?
Replace a string as a set rather than mixing new units into old ones. Units of different ages, and models of different capacities, settle at different internal resistances, so a mixed string shares current unevenly on discharge and float, which shortens the life of the new batteries and hides the condition of the old. A specialist can price the full set with volume freight in one quote.
Order online at the minimum of four, or send the quantity, your delivery ZIP and your requested-by date. A specialist confirms availability, the warranty term, volume pricing and freight in writing, with no obligation to buy.
Call 1-877-775-4381 · battery specialists, not a call centerWARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov (State of California only).