CSB XTV12800 12V 80AH Group 24 Extreme Temperature AGM Deep Cycle Battery
CSB XTV12800 12V 80AH Group 24 Extreme Temperature AGM Deep Cycle Battery
CSB XTV12800 Battery - 12V 80Ah Extreme Temperature AGM, Group 24
Warranty
Where 800 Amps Starts
- 80.0 Ah at the 20 hour rate - to 1.75 volts per cell at 25°C, matching the CSB price list to the decimal, with 74.2 Ah at the 8 hour rate.
- 1,917 amps short circuit current - for 5 seconds, the figure a DC protection study needs before a string is energized.
- 24 amps maximum charge current - a recharge ceiling that a small cabinet charger will not reach, so recovery time is set by the charger rather than the battery.
- Approximately 4.70 milliohms internal resistance - the day-one baseline for a conductance program, and half a milliohm below the 22NF block.
- Made to order - a non-stock part on the CSB price list; the lead time is the factory's and we quote it, not a stock date.
Technical Specifications
| CSB XTV12800 Specifications | |
|---|---|
| Part Number | XTV12800 (also written XTV 12800, XTV-12800 and xtv12800) |
| Series | XTV, Extreme Temperature, 12 volt top terminal |
| Battery Type | AGM, valve regulated lead acid (VRLA), pure lead construction |
| Nominal Voltage | 12V |
| Capacity, 20 Hour Rate | 80.0 Ah to 1.75 VPC at 25°C (CSB price list lists 80 Ah) |
| Capacity, 8 Hour Rate | 74.2 Ah to 1.75 VPC; 73.0 Ah to 1.80 VPC |
| Watts Per Battery, 15 Minutes | 1,618 W to 1.67 VPC at 25°C (CSB XTV series tables, RA240531) |
| Discharge Current, 60 Minutes | 54.2 A to 1.67 VPC at 25°C |
| Discharge Current, 5 Hours | 14.2 A to 1.67 VPC at 25°C |
| Maximum Charge Current | 24 A |
| Maximum Discharge Current | 800 A for 5 seconds |
| Short Circuit Current | 1,917 A for 5 seconds |
| Internal Resistance | Approximately 4.70 milliohms |
| Terminal Type | I2 threaded lead alloy insert to accept an M6 bolt |
| Terminal Torque | 44.9 ± 9.0 lbf-in (5.1 ± 0.6 N·m) |
| Length | 10.28 ± 0.10 inches (261.0 ± 2.5 mm) |
| Width | 6.63 ± 0.08 inches (168.5 ± 2.0 mm) |
| Height | 8.41 ± 0.10 inches (213.5 ± 2.5 mm) |
| Weight | 56.20 lbs (25.50 kg) |
| BCI Group Size | 24 (CSB price list) |
| Float Charging Voltage | 13.5 to 13.8 VDC per battery at 25°C (77°F) |
| Equalization Charging Voltage | 14.4 to 15.0 VDC per battery at 25°C (77°F) |
| Operating Temperature | Nominal 25°C (77°F); discharge -20°C to 50°C (5°F to 122°F); charge and storage -20°C to 40°C (5°F to 104°F) |
| Self Discharge | Less than 10 percent after 90 days at 25°C; store up to 6 months, or 10 months with an equalization charge, then recharge fully before use |
| Container Material | Polypropylene (UL 94-HB); flame retardant 94-V0 available on request, priced as a surcharged option on the CSB price list |
| Standards | IEC 60896-21/22:2004; UL1973 Listed (MH66728); UL1989 Recognized (MH14533); TUV NORD to ISO 9001:2015 |
| Design Life | Up to 12 years in standby service at 25°C; greater than 12 years on the Eurobat 20°C basis |
| Warranty | 4 years (CSB, XTV Taiwan build) |
| Country of Origin | Taiwan |
| Stock Status at CSB | Build-to-order (non-stock on the CSB price list) |
Where This Battery Is Used
- 48 volt outdoor telecom strings - four blocks carrying a macro or micro site through a multi-hour outage in an unconditioned cabinet.
- Off-grid and solar-hybrid monitoring - float service with periodic deep discharge, where the temperature rating and the 12 year design life both earn their cost.
- Utility substation and switchgear backup - outdoor control houses where a group 24 tray is already on the drawing.
Ordering and Freight
Frequently Asked Questions
Why do three different sizes share an 800 amp discharge limit?
Because the limit lives at the terminal. The XTV12800, XTV121000 and XTV121100 all carry I2 alloy inserts on M6 bolts and all publish 800 amps for 5 seconds. The plate groups differ, which is why the short circuit figures climb from 1,917 amps here to 2,258 and 2,648 above, and why internal resistance falls from 4.70 milliohms to 4.10 and 3.60. Use 800 amps to check inrush on the load. Use the short circuit figure to size the protection. Do not use either to compare battery capacity.
How long will this hold a 48 volt load?
The datasheet answers in amps and watts per battery over time. At 1.67 volts per cell this block sustains 54.2 amps for one hour, 14.2 amps for five hours, and 7.75 amps for ten. A 48 volt string of four delivers those same currents at four times the voltage, so a 650 watt load at 48 volts draws about 13.5 amps and sits close to the five hour line. Work from the current the load draws, not from the amp hour badge, and leave margin for the cold end of the range where capacity falls.
Is 24 amps of charge current a problem for a small cabinet charger?
The opposite. It is a ceiling, and most outdoor cabinet rectifiers will not approach it, so the battery accepts whatever the charger can give. The consequence is that recovery time after a deep discharge is set by the charger's output rather than by the battery. A 10 amp charger will take the better part of a day to bring an 80 Ah block back from a full discharge. Plan the recovery window around the charger's output rather than the datasheet's ceiling.
Why is the 8 hour rating 74.2 Ah when the badge says 80?
Because the badge is the 20 hour figure. Lead acid capacity depends on how fast you take it out: at the 20 hour rate this block delivers 80.0 Ah to 1.75 volts per cell, at the 8 hour rate 74.2 Ah, and at one hour it sustains 54.2 amps, which is about 54 Ah. A four hour outdoor hold sits between the last two. When a runtime calculation uses 80 Ah for a four hour discharge it overstates the result by roughly a fifth, and on a cabinet that has to make it to morning that fifth is the difference. Size from the discharge table at the rate the load draws.
Give a specialist the load in watts, the hold time and the coldest ambient on record at the site. The 80, 100 and 110 Ah blocks share a terminal and a ceiling and differ on runtime, and that calculation picks between them.
Call 1-877-775-4381 · battery specialists, not a call centerWARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov (State of California only).