CSB MSJ-500 2V VRLA AGM Battery - 500AH Maintenance-Free Standby Power
CSB MSJ-500 2V VRLA AGM Battery - 500AH Maintenance-Free Standby Power
CSB MSJ-500 Battery - 2V 506 Ah Pure Lead AGM Cell for High Capacity Float
Warranty
Where the Protective Device Design Has to Be Revisited
- 830 amps and 1,508 watts at 15 minutes - to 1.67 volts per cell at 25°C, the column a generator transfer window gets sized against.
- 150.00 amps maximum charge current - the recharge ceiling, 25 percent above the MSJ-400 and half that of the MSJ-1000.
- 3,000 amps over 5 seconds - the published peak, which is inrush headroom rather than a sustained rating.
- 6.73 inches wide and 13.15 inches tall - the same cross section as the MSJ-1000, so the two sizes share a tier layout and differ only in depth.
- Equalization at 2.35 VDC per cell - with the float band running 2.21 to 2.25 VDC per cell, both referenced to 25°C (77°F); a room that runs warm belongs at the low end of the float band.
Technical Specifications
| CSB MSJ-500 Specifications | |
|---|---|
| Part Number | MSJ-500 (also searched as MSJ500, MSJ 500 and msj-500) |
| Series | MSJ, 2 volt high capacity, top terminal |
| Battery Type | AGM, valve regulated lead acid (VRLA), pure lead construction |
| Nominal Voltage | 2V |
| Capacity, 8-Hour Rate | 506.40 Ah to 1.75 VPC at 25°C (77°F) |
| Capacity, 20-Hour Rate | 524.00 Ah to 1.75 VPC at 25°C |
| Capacity, 8-Hour Rate to 1.80 VPC | 493.60 Ah at 25°C |
| Discharge, 15 Minutes | 830 A and 1,508 W to 1.67 VPC at 25°C |
| Discharge, 1 Hour | 345 A to 1.75 VPC at 25°C |
| Discharge, 8 Hours | 63.3 A and 125 W to 1.75 VPC at 25°C |
| Maximum Charge Current | 150.00 A |
| Maximum Discharge Current | 3000 A (5 second rate) |
| Short Circuit Current | 9,953 A |
| Internal Resistance | Approximately 0.28 milliohms |
| Terminal Type | I4 threaded copper alloy insert, accepts an M8 bolt |
| Terminal Torque | 109 ±22 lbf-in (126 ±25 kgf-cm, 12.3 ±2.5 N-m) |
| Depth | 9.49 inches (241.0 mm) |
| Width | 6.73 inches (171.0 mm) |
| Height | 13.15 inches (339.0 mm) |
| Weight | 80.45 lbs (36.50 kg) |
| Float Charging Voltage | 2.21 to 2.25 VDC per cell at 25°C (77°F) |
| Equalization Charging Voltage | 2.35 VDC per cell at 25°C (77°F) |
| Operating Temperature | Nominal 25°C (77°F); discharge -15°C to 50°C (5°F to 122°F); charge and storage -15°C to 40°C (5°F to 104°F) |
| Self Discharge | Less than 10 percent after 90 days at 25°C; storable to six months, and to ten months with an equalization charge |
| Container Material | Flame retardant ABS (UL 94-V0) |
| Standards | IEC 60896-21/22:2004; UL1973 Listed (MH66728); UL1989 Recognized (MH14533); TUV NORD to ISO 9001:2015 |
| Design Life | Up to 20 years in standby service at 25°C; greater than 12 years on the Eurobat 20°C basis |
| Warranty | 5 years (CSB, MSJ 2 volt range) |
| Country of Origin | Taiwan |
Where This Battery Is Used
- Large central office DC plant - 24 cell strings on a -48 volt bus carrying eight hours or more of reserve for a whole building.
- Generating station and substation DC systems - 60 cell and 120 cell banks under IEEE sizing practice, where the duty cycle has a defined first minute.
- Renewable and microgrid storage on float - banks that idle at full charge for long periods and are judged on how they look after a decade.
Ordering and Freight
Frequently Asked Questions
Why does short circuit current jump so far above the MSJ-400?
Short circuit current is set by internal resistance and cell construction, and it does not track capacity in a straight line. Internal resistance falls from 0.30 to 0.28 milliohms across that step, and CSB's measured result is 9,953 amps against 6,065. The practical consequence is that a protective device and its interrupting rating are sized off the fault figure, so an upgrade from a 400 bank to a 500 bank is an electrical review and not only a capacity swap.
MSJ-500 or MSJ-1000 for a 500 amp hour requirement?
The MSJ-500 meets it in one cell per position. Choosing the MSJ-1000 would give roughly double the reserve at double the weight and double the depth, which is the right move where the reserve target is going up later and the floor loading allows it. Where 500 Ah is the settled requirement, the MSJ-500 is the correct size and the lighter install. We will say so rather than sell the larger cell.
What torque goes on the M8 terminal bolt?
109 lbf-in, with a tolerance of plus or minus 22, which is 12.3 N-m plus or minus 2.5. Copper alloy inserts take a higher torque than the lead alloy inserts on CSB's 12 volt lines, and under-torquing is the more common error because installers carry over a figure from a smaller battery. Use a calibrated torque wrench on every connection and record the reading.
How long can these sit before commissioning?
Self discharge is under 10 percent after 90 days at 25°C. Storage runs to six months as shipped, and to ten months if an equalization charge is applied part way through. A full recharge is required before the bank goes into service either way, and a warmer stockroom shortens every one of those windows. Tell us the install date and the cells get dated to suit it.
Send the cell going out, the bus voltage and the protective device ratings you have in place. A specialist checks the fault figures against your design before quoting the string and freight in writing.