CSB HR1227W F2 Battery - 12V High Rate VRLA, 27 Watts Per Cell at 15 Minutes
Warranty
The Strong Small Brick
- Sealed VRLA-AGM construction - recombination rated up to 99% by CSB, no maintenance.
- IEC 61056-1/2:2012 built, UL1973 Listed (MH66728), UL1989 Recognized (MH14533) - the file numbers printed on the CSB datasheet linked below.
- Wide discharge window - rated for discharge from -15°C up to +50°C when the install is less than ideal.
Technical Specifications
| CSB HR1227W F2 Specifications | |
|---|---|
| Part Number | HR1227W F2 (also searched as HR1227WF2, HR 1227W F2, CSB HR1227W) |
| Battery Type | VRLA-AGM, high rate, top terminal |
| Nominal Voltage | 12V |
| Power Rating, 15-minute | 27.0 watts per cell to 1.67 VPC at 77°F (162 W per battery) |
| Power Rating, 5-minute | 53.0 watts per cell to 1.67 VPC |
| Max Discharge Current | 130 A (F2 build; the F1 build is rated 100 A) |
| Short Circuit Current | 424 A |
| Internal Resistance | Approx. 19.9 milliohms |
| Terminal Type | F2 Faston tab, 0.250 inch |
| Length | 3.54 inches (90.0 mm) |
| Width | 2.76 inches (70.0 mm) |
| Height | 4.18 inches (106.1 mm) |
| Weight | 4.34 lbs (1.97 kg) |
| Container | ABS (UL 94-HB); flame-retardant 94-V0 build available on request |
| Operating Temperature | Discharge -15°C to +50°C; charge and storage -15°C to +40°C |
| Float Charging Voltage | 13.5 to 13.8 Vdc per battery at 77°F |
| Country of Origin | Vietnam |
| Design Life | Up to 5 years standby at 77°F (CSB) |
| Warranty | 1 year (CSB) |
Where This Battery Is Used
- Compact UPS units carrying real load - the small-case models that protect network gear rather than a single desktop.
- Telecom and security equipment holdover - short-window power where cabinet space is fixed.
Ordering and Shipping
Frequently Asked Questions
Why does a small UPS need a high-rate battery at all?
Because of how the rating is earned. A battery rated for 20-hour discharges delivers a shrinking fraction of its energy as the draw gets faster, and a UPS empties its battery in minutes. The HR series is rated in watts per cell over 15 minutes, the window a UPS runs. In this case size, that is the difference between the runtime you calculated and the runtime you get.
My old battery has narrower terminal tabs. Is that a problem?
The narrow tab is the F1; this listing carries the 0.250-inch F2. The two do not mate without an adapter, and an adapter adds a resistance point right where the current is highest. CSB builds this model in an F1 version, rated 100 A maximum discharge, and we quote it on request. Match what your connector takes and say which tab you need on the quote.
Can the HR1227W live in a hot closet?
It is rated to discharge at ambient temperatures up to 122°F, so it will do its job in the heat. Living there is a different matter: every VRLA battery ages faster above 77°F, and the design life figure assumes that cooler number. If the closet runs hot year round, plan a shorter replacement cycle or move air through the space, whichever costs the site less.
How long can a spare HR1227W sit on the shelf?
The CSB datasheet gives up to 6 months at 77°F, with self-discharge under 10% over the first 90 days. Warmer storage shortens that window, so shelve spares somewhere cool and recharge them inside it.
Send the quantity, your delivery ZIP and your requested-by date. A specialist confirms the terminal build, availability, the warranty term and shipping in writing, with no obligation to buy.
Call 1-877-775-4381 · battery specialists, not a call centerWARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov (State of California only).