C&D BBG-220RT Broadband GEL Battery
C&D BBG-220RT Broadband GEL Battery
C&D BBG-220RT Battery - 12V 220 Minute Broadband Gel VRLA
Warranty
Built for the Enclosure That Swings
- Gel chemistry for temperature extremes - C&D's own zone map places the BBG line at 40 degrees latitude and above and at 30 degrees and below, and leaves the middle zones open to either technology.
- Float band 13.5 to 13.8 VDC per unit - average at 77°F (25°C), the setting a cable power supply's charger holds between outages.
- Inter unit connectors and racks - both listed as available accessories for the Broadband series, which matters when a pedestal retrofit changes the block spacing.
- Nominal operating window of +74°F to +80°F - C&D's stated normal range for the series, and the band an enclosure's ventilation should be aiming at.
- Polyethylene separators - unlike an AGM mat, they hold float current down as the cabinet warms, which is where a gel block earns its place in an uncontrolled location.
Technical Specifications
| C&D BBG-220RT Specifications | |
|---|---|
| Part Number | BBG-220RT (also searched as bbg 220 rt, BBG220RT and 220RT; C&D Broadband gel series) |
| Series | Broadband BBG, gelled VRLA design |
| Battery Type | Gel VRLA, gelled electrolyte with polyethylene separators |
| Nominal Voltage | 12V (6 cells per unit) |
| Runtime Rating | 220 minutes at a 25 A constant current load to 1.75 VPC at 77°F (25°C) |
| Constant Current to 1.75 VPC | 67.70 A for 1 hr, 40.40 for 2 hr, 29.10 for 3 hr, 22.90 for 4 hr, 16.10 for 6 hr, 12.60 for 8 hr, 10.20 for 10 hr, 8.70 for 12 hr, 5.50 for 20 hr, 4.60 for 24 hr, 2.40 for 48 hr, 1.60 for 72 hr, 1.20 for 100 hr (all at 77°F) |
| Ampere-Hour Rating | No published figure; C&D rates the Broadband series in runtime minutes and constant current amperes |
| Maximum Discharge Current | 800 A |
| Short Circuit Current | 2,600 A |
| Terminal Type | 1/4-20 UNC bolt |
| Terminal Torque | 110 in-lbs (12.4 N-m) |
| Length | 13.42 inches (341 mm) |
| Width | 6.80 inches (173 mm) |
| Height | 8.48 inches (215 mm) |
| Weight | 73 lbs (33 kg) |
| Float Charging Voltage | 13.5 to 13.8 VDC per unit average at 77°F (25°C) |
| Recommended Maximum Charging Current | C20/5 amperes (23.12 A) |
| Maximum AC Ripple | 0.5% RMS or 1.5% P-P of float charge voltage recommended; 1.4% RMS (4% P-P) allowed; 4.6 A RMS current allowed (C20/20) |
| Operating Temperature | Discharge -40°F to +160°F (-40°C to +71°C); charge -10°F to +140°F (-23°C to +60°C) with temperature compensation |
| Nominal Operating Temperature | +74°F to +80°F (23°C to 27°C) |
| Self Discharge | 18 months at 77°F (25°C), then a freshening charge is required |
| Accessories | Inter unit connectors and racks available |
| Design Life | No published design life; C&D states a 5+ year service life for the BBG gel series |
| Warranty | 2 years (C&D Broadband series limited warranty, gelled VRLA design) |
| Minimum Order | 4 units |
Where This Battery Is Used
- Northern and southern CATV plant - the latitude bands where C&D specifies gel over AGM for the enclosure temperature alone.
- Long-carriage standby supplies - nodes and amplifier cascades held up for the longest runtime the gel line offers.
- Security and industrial UPS cabinets - two further markets C&D lists for the Broadband series, on the same float and the same terminal hardware.
Ordering and Freight
Frequently Asked Questions
Does the 220 in BBG-220RT mean 220 amp hours?
No. It is 220 minutes at a 25 amp constant current load, measured to 1.75 volts per cell at 77°F. C&D names every block in the Broadband range by that runtime figure and publishes no ampere-hour rating for the series at all. A sizing worksheet written around amp-hours needs the constant current table instead: 67.70 amps for one hour, 12.60 for eight, 5.50 for twenty.
How long will a BBG-220RT run a 16 amp load?
Six hours to 1.75 volts per cell at 77°F, with 16.10 amps sitting on that column. Drop the load to 12.60 amps and the block runs eight hours; raise it to 22.90 and it runs four. A 36 volt supply built from three blocks pulling 16 amps therefore holds about 580 watts for six hours at room temperature. Enclosure temperature moves all of it, so quote the site ambient alongside the load.
Where does the BBG-220RT sit against the BBA-240PLP?
Twenty minutes of runtime apart and a different chemistry underneath. The 240PLP is a pure lead AGM at 240 minutes and 75 lbs; the 220RT is gel at 220 minutes and 73 lbs, on the identical 13.42 by 6.80 by 8.48 inch case. C&D's guidance is geographic rather than numeric: gel in the hottest and coldest zones, either technology between 30 and 39 degrees latitude, where the AGM's longer service life and higher runtime come into play.
Does a BBG-220RT need a freshening charge before it goes into service?
It depends how long it has been sitting. C&D rates a stored gel block for 18 months at 77°F before a freshening charge is required, and the interval shortens as storage temperature rises. Check the date code against that window before a block goes on the strand, because a partially self-discharged cell put straight onto float in a hot pedestal starts its service behind. Ask for the date code with your quote.