C&D BBG-195RT Broadband GEL Battery

$326.95
SKU: BBG-195RT
Availability: Request Quote For Availability
Shipping: Free shipping on orders $75 and up
Voltage: 12
Chemistry: Gel VRLA, gelled electrolyte, polyethylene separators
Features: Broadband
Terminal: 1/4-20 UNC bolt, 110 in-lbs (12.4 N-m)
Minimum Order Quantity: 4 Batteries
Capacity: 195 minutes at a 25 A constant current load to 1.75 VPC at 25C; 65.10 A for 1 hour, 11.50 A for 8 hours
Dimensions: 13.42 x 6.80 x 8.48 in
C&D BBG-195RT Broadband GEL Battery

C&D BBG-195RT Broadband GEL Battery

$326.95
Adding to cart… The item has been added

C&D BBG-195RT Battery - 12V 195 Minute Broadband Gel VRLA

When the supply comes up short of the carriage time the site is held to and the pedestal has no room for a fourth block, the fifteen minute step to a BBG-195RT is what a plant engineer buys: 195 minutes at a 25 amp constant current load to 1.75 volts per cell at 77°F, between the 180RT and the 220RT in C&D's Broadband gel line. It sits on the 13.42 by 6.80 by 8.48 inch case C&D uses across most of the broadband range, at 66 lbs, so an enclosure already cut for a 220RT or a 240PLP takes it without a bracket change. The full discharge table runs from 65.10 amps for one hour to 1.10 amps for a hundred.

Warranty

Warranty. C&D's term on the Broadband gel series is 2 years, under C&D's Broadband series limited warranty. Design life is a separate figure: C&D publishes no design life for the gel series and states a 5+ year service life. Terms are confirmed in writing with your quote.

The Middle Step in the Gel Line

195 minutes at 25 amps
Fifteen minutes over the BBG-180RT and twenty-five under the BBG-220RT, measured to 1.75 volts per cell at 77°F.
11.5 amps over eight hours
14.80 amps for six hours, 9.50 for ten, 5.00 for twenty, if the duty is a long low-current hold and not a short outage.
66 lbs on the 13.42 inch case
Three pounds over the 180RT and seven under the 220RT, on the same 6.80 by 8.48 inch cross section as the AGM blocks.
  • 1/4-20 UNC terminal at 110 in-lbs - C&D specifies the same bolt and the same 12.4 N-m torque on every broadband model, gel and AGM alike.
  • Charger ripple ceiling - 0.5 percent RMS or 1.5 percent peak to peak of float voltage for best results, with 1.4 percent RMS (4 percent P-P) and 4.6 amperes RMS the published maximums.
  • Eighteen months on the shelf - a stored gel block is rated 18 months at 77°F before a freshening charge falls due, and the interval shortens at higher storage temperatures.
  • Discharge window -40°F to +160°F - charging runs a narrower -10°F to +140°F and needs temperature compensation across that span.
  • 2,500 amps short circuit - 200 amps above the 180RT and 100 below the 220RT, against the 800 amp maximum discharge current common to the series.

Technical Specifications

C&D BBG-195RT Specifications
Part NumberBBG-195RT (also searched as BBG 195RT, BBG195RT and 195RT; C&D Broadband gel series)
SeriesBroadband BBG, gelled VRLA design
Battery TypeGel VRLA, gelled electrolyte with polyethylene separators
Nominal Voltage12V (6 cells per unit)
Runtime Rating195 minutes at a 25 A constant current load to 1.75 VPC at 77°F (25°C)
Constant Current to 1.75 VPC65.10 A for 1 hr, 37.40 for 2 hr, 26.80 for 3 hr, 21.00 for 4 hr, 14.80 for 6 hr, 11.50 for 8 hr, 9.50 for 10 hr, 8.00 for 12 hr, 5.00 for 20 hr, 4.30 for 24 hr, 2.20 for 48 hr, 1.50 for 72 hr, 1.10 for 100 hr (all at 77°F)
Ampere-Hour RatingNo published figure; C&D rates the Broadband series in runtime minutes and constant current amperes
Maximum Discharge Current800 A
Short Circuit Current2,500 A
Terminal Type1/4-20 UNC bolt
Terminal Torque110 in-lbs (12.4 N-m)
Length13.42 inches (341 mm)
Width6.80 inches (173 mm)
Height8.48 inches (215 mm)
Weight66 lbs (30 kg)
Float Charging Voltage13.5 to 13.8 VDC per unit average at 77°F (25°C)
Recommended Maximum Charging CurrentC20/5 amperes (23.12 A)
Maximum AC Ripple0.5% RMS or 1.5% P-P of float charge voltage recommended; 1.4% RMS (4% P-P) allowed; 4.6 A RMS current allowed (C20/20)
Operating TemperatureDischarge -40°F to +160°F (-40°C to +71°C); charge -10°F to +140°F (-23°C to +60°C) with temperature compensation
Nominal Operating Temperature+74°F to +80°F (23°C to 27°C)
Self Discharge18 months at 77°F (25°C), then a freshening charge is required
AccessoriesInter unit connectors and racks available
Design LifeNo published design life; C&D states a 5+ year service life for the BBG gel series
Warranty2 years (C&D Broadband series limited warranty, gelled VRLA design)
Minimum Order4 units

Where This Battery Is Used

  • Cable plant power supplies on a fixed carriage target - where the supply has to reach a stated number of minutes and the next runtime step is the only way to get there.
  • Reverse power and return path equipment - listed by C&D among the Broadband markets, on the same float charge as the forward plant.
  • Traffic management and signal cabinets - roadside enclosures that swing with the weather and are serviced on a route.

Ordering and Freight

Minimum order is 4 units. At 66 lbs per block a set ships freight pre-paid by LTL to a commercial address; a residential or limited-access delivery adds $100, which is the liftgate and access charge the carrier bills us. Send the quantity, your delivery ZIP and your requested-by date, and a specialist returns a written quote with volume pricing in 24 to 48 hours.

Frequently Asked Questions

How much extra runtime does the BBG-195RT give over the BBG-180RT?

Fifteen minutes at the 25 amp reference load, 195 against 180. The gap widens at lower currents: 5.00 amps for twenty hours against 4.30, and 11.50 amps for eight hours against 10.00, both to 1.75 volts per cell at 77°F. That is roughly 15 percent more current across the long columns for three extra pounds and a taller case. If the pedestal clears 8.48 inches, the step is usually worth taking.

Will a BBG-195RT drop into a pedestal cut for a BBG-220RT?

Physically, yes. Both sit on the same 13.42 by 6.80 by 8.48 inch case with the same 1/4-20 UNC terminals, and the 195RT is seven pounds lighter. What does not carry across is the sizing: the 220RT holds 25 more minutes at the reference load and 0.50 amps more on the twenty-hour column, so a supply sized on 220 minutes loses carriage time if it is refilled with 195s. Match the runtime to the specification, not to the case.

What does a BBG-195RT hold on a two-hour discharge?

37.40 amps to 1.75 volts per cell at 77°F. Three blocks in series at 36 volts therefore carry about 1.3 kW for two hours before the cutoff, and four blocks at 48 volts carry about 1.8 kW. The three-hour column drops to 26.80 amps and the four-hour to 21.00. Send the supply's output rating and the carriage time the site is held to, and the block count comes off the table.

How many BBG-195RT blocks does a 36 volt cable power supply take?

Three in series, since each block is 12 volts nominal with six cells. A 24 volt supply takes two and a 48 volt plant takes four. The minimum order of four covers a 48 volt string outright, or a 36 volt string with a spare. Inter unit connectors and racks are available if the enclosure needs new hardware for the swap.

Next runtime up: C&D BBG-220RT220 minutes at 25 amps on the same 13.42 inch case, at 73 lbs and 2,600 amps short circuit.