CSB XPL4700 Battery - 12V 4700W High-Rate VRLA AGM, UPS Standby Power
CSB XPL4700 Battery - 12V 4700W High-Rate VRLA AGM, UPS Standby Power
CSB XPL4700 Battery - 12V 100 Ah Extreme Power Long Life AGM
Warranty
The Same Weight as an HRL12390W, With More Behind It
- Group 27 case at 12.15 inches long - 6.65 inches wide and 8.41 inches tall, so shelf depth is what decides a retrofit rather than the width or height.
- 1,050 amps over 5 seconds - peak discharge as published, which is headroom for inrush rather than a sustained rating.
- 39.20 amps maximum charge current - the recovery ceiling after a deep discharge on a large string.
- Pure lead plates with proprietary elements - the Extreme Power construction, and the reason the design life figure reaches ten years on float.
- Float held 13.5 to 13.8 VDC per battery - measured at 25°C (77°F); the equalization window runs 14.4 to 15.0 VDC per battery at that same temperature.
Technical Specifications
| CSB XPL4700 Specifications | |
|---|---|
| Part Number | XPL4700 (also searched as XPL 4700, XPL4700FR and xpl4700; CSB prints the flame retardant build as XPL 4700FR) |
| Series | XPL, Extreme Power long life, top terminal |
| Battery Type | AGM, valve regulated lead acid (VRLA), pure lead construction |
| Nominal Voltage | 12V |
| Nominal Capacity | 100 Ah at the 20-hour rate to 1.75 VPC at 25°C (77°F), per the CSB price list; the per-part datasheet rates this series in watts only |
| Watts Per Cell, 15 Minutes | 438 W to 1.67 VPC at 25°C |
| Watts Per Cell, 5 Minutes | 758 W to 1.67 VPC at 25°C |
| Watts Per Cell, 30 Seconds | 1,055 W to 1.67 VPC at 25°C |
| Maximum Charge Current | 39.20 A |
| Maximum Discharge Current | 1050 A (5 second rate) |
| Short Circuit Current | 2,759 A |
| Internal Resistance | Approximately 2.86 milliohms |
| Terminal Type | I2 threaded lead alloy insert, accepts an M6 bolt |
| Terminal Torque | 44.9 ±9.0 lbf-in (51.7 ±10.3 kgf-cm, 5.10 ±1.0 N-m) |
| Length | 12.15 inches (308.7 mm) |
| Width | 6.65 inches (169.0 mm) |
| Height | 8.41 inches (213.6 mm) |
| Weight | 72.73 lbs (33.00 kg) |
| BCI Group Size | 27 |
| Float Charging Voltage | 13.5 to 13.8 VDC per battery at 25°C (77°F) |
| Equalization Charging Voltage | 14.4 to 15.0 VDC per battery at 25°C (77°F) |
| Operating Temperature | Nominal 25°C (77°F); discharge -15°C to 50°C (5°F to 122°F); charge and storage -15°C to 40°C (5°F to 104°F) |
| Self Discharge | Less than 10 percent after 90 days at 25°C; storable to six months before a full recharge |
| Container Material | Polypropylene (UL 94-HB); flame retardant 94-V0 available on request |
| Standards | IEC 60896-21/22:2004; UL1973 Listed (MH66728); UL1989 Recognized (MH14533); TUV NORD to ISO 9001:2015 |
| Design Life | Up to 10 years in standby service at 25°C; greater than 12 years on the Eurobat 20°C basis |
| Warranty | 5 years (CSB, XPL Extreme Power range) |
| Country of Origin | Taiwan |
Where This Battery Is Used
- Large UPS cabinets - strings carrying a rack row or a floor, sized on the 15 minute column.
- Colocation and data center plant - float duty measured in years between events, where design life justifies the size.
- Replacing an HRL string at the same weight - where the shelf rating is already proven and the requirement is a longer term.
Ordering and Freight
Frequently Asked Questions
XPL4700 or HRL12390W?
Both are 100 Ah and both weigh 72.73 lbs, so the decision is not about capacity or handling. The XPL delivers 438 watts per cell at 15 minutes against the HRL's 414, carries 2.86 milliohms against 3.00, and holds a 5 year CSB term against 4. The HRL case is 1.35 inches shorter at 12.15 against 13.50, which occasionally decides it. If the shelf takes either, the XPL is the stronger specification.
What does the 4700 in the name refer to?
The block's nominal output at the 5 minute rate. Six cells at 758 watts each come to 4,549 watts, which CSB rounds to 4700. The badge sits about 3 percent above the measurement, and every model in the range is nominal in the same direction, so a worksheet built on model numbers will slightly over-estimate the string. Size from the per-cell figure at your required duration.
Can I mix XPL and HRL blocks in one string?
No, and we will say so before taking the order. The two lines have different internal resistance and different discharge characteristics, so a mixed string is governed by its weakest section and charges unevenly. If you are replacing part of an HRL bank, either finish the bank in HRL or replace the whole string in XPL. A part-replacement that saves money this year usually costs a full string next year.
How does it behave above 25 degrees?
Design life is quoted at a 25°C (77°F) nominal, and every degree above that shortens it. Discharge is rated from -15°C to 50°C, so the block will work in a warm room, but the ten year figure assumes the nominal. Tell us your actual ambient and a specialist will say what it does to the replacement interval before you commit.
Send the part number you run now, the quantity and the shelf you have. A specialist puts the two side by side on the figures that matter and quotes both in writing.