CSB XPL4200 12V 661W/Cell 5-Min Pure Lead AGM UPS Battery
CSB XPL4200 12V 661W/Cell 5-Min Pure Lead AGM UPS Battery
CSB XPL4200 Battery - 12V 85 Ah Extreme Power Long Life AGM
Warranty
Same Capacity, More Power
- 900 amps over 5 seconds - peak discharge as CSB publishes it, which is inrush headroom and not a rating you can sustain.
- 35.00 amps maximum charge current - the recovery ceiling; confirm your rectifier can be held at or under it before the string goes in.
- 980 watts per cell at 30 seconds - published for this model, which matters if the application turns on a sub-minute event rather than a timed ride-through.
- I2 threaded insert for an M6 bolt - torqued to 44.9 plus or minus 9.0 lbf-in (5.10 plus or minus 1.0 N-m), so existing cable lugs carry across from the 3500.
- Built to IEC 60896-21/22:2004 - UL1973 Listed under MH66728, UL1989 Recognized under MH14533, with TUV NORD certification to ISO 9001:2015.
Technical Specifications
| CSB XPL4200 Specifications | |
|---|---|
| Part Number | XPL4200 (also searched as XPL 4200, XPL4200FR and xpl4200; CSB prints the flame retardant build as XPL 4200FR) |
| Series | XPL, Extreme Power long life, top terminal |
| Battery Type | AGM, valve regulated lead acid (VRLA), pure lead construction |
| Nominal Voltage | 12V |
| Nominal Capacity | 85 Ah at the 20-hour rate to 1.75 VPC at 25°C (77°F), per the CSB price list; the per-part datasheet rates this series in watts only |
| Watts Per Cell, 15 Minutes | 370 W to 1.67 VPC at 25°C |
| Watts Per Cell, 5 Minutes | 661 W to 1.67 VPC at 25°C |
| Watts Per Cell, 30 Seconds | 980 W to 1.67 VPC at 25°C |
| Maximum Charge Current | 35.00 A |
| Maximum Discharge Current | 900 A (5 second rate) |
| Short Circuit Current | 2,616 A |
| Internal Resistance | Approximately 3.22 milliohms |
| Terminal Type | I2 threaded lead alloy insert, accepts an M6 bolt |
| Terminal Torque | 44.9 ±9.0 lbf-in (51.7 ±10.3 kgf-cm, 5.10 ±1.0 N-m) |
| Length | 10.28 inches (261.0 mm) |
| Width | 6.63 inches (168.5 mm) |
| Height | 8.41 inches (213.5 mm) |
| Weight | 62.17 lbs (28.20 kg) |
| Float Charging Voltage | 13.5 to 13.8 VDC per battery at 25°C (77°F) |
| Equalization Charging Voltage | 14.4 to 15.0 VDC per battery at 25°C (77°F) |
| Operating Temperature | Nominal 25°C (77°F); discharge -15°C to 50°C (5°F to 122°F); charge and storage -15°C to 40°C (5°F to 104°F) |
| Self Discharge | Less than 10 percent after 90 days at 25°C; storable to six months before a full recharge |
| Container Material | Polypropylene (UL 94-HB); flame retardant 94-V0 available on request |
| Standards | IEC 60896-21/22:2004; UL1973 Listed (MH66728); UL1989 Recognized (MH14533); TUV NORD to ISO 9001:2015 |
| Design Life | Up to 10 years in standby service at 25°C; greater than 12 years on the Eurobat 20°C basis |
| Warranty | 5 years (CSB, XPL Extreme Power range) |
| Country of Origin | Taiwan |
Where This Battery Is Used
- UPS cabinets sized on ride-through - where the requirement is stated in minutes at a load rather than in amp hours.
- Industrial control and automation - plant that has to hold its state through a utility event and restart cleanly.
- Data rooms replacing a same-capacity string - where the old bank met its amp hour spec but never made its runtime.
Ordering and Freight
Frequently Asked Questions
How can the 4200 and 3500 both be 85 Ah?
Because amp hours and power are different measurements. Capacity is measured drawing a small current for 20 hours; power is measured drawing hard for minutes. CSB builds both blocks in the same case on the same capacity and configures the plates differently, so the 4200 delivers 370 watts per cell at 15 minutes where the 3500 gives 318. If you specify from the capacity column you will treat these two as interchangeable, and on a UPS they are not.
Which figure should I size from?
The watts per cell at the duration you need to ride, then the number of cells in the string. A UPS discharges hard and briefly, and the amp hour rating is measured under conditions nothing in a UPS cabinet resembles. Use capacity to sanity-check against a competing part, and use watts per cell to decide.
Is the 4200 a drop-in for a 3500?
Physically yes. Same 10.28 by 6.63 inch case, same 8.41 inch height, same I2 insert and the same torque, so the shelf and the cable lugs are unchanged. The shelf has to take 5.31 more pounds per block, and the charger has to allow up to 35.00 amps rather than 29.20. Confirm those two and the swap is straightforward.
What is the 30 second rating for?
Motor inrush and the first instant of a transfer, where the load spikes well above its steady draw. CSB publishes 980 watts per cell at 30 seconds for the 4200. If your load has a large inrush component, that column matters as much as the 15 minute one, and it is a figure the 3500 does not publish at all.
Send the load in watts and the minutes you need. A specialist works the string from the per-cell figures and puts the result in writing, with no obligation to buy.
Call 1-877-775-4381 · battery specialists, not a call centerWARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov (State of California only).