C&D TEL12-105FHTG Battery - 12V 101Ah TEL-HT Front Access
Warranty
The Compact High-Temperature Build
- MSE pure lead construction - the grid technology behind the line's 12+ year design life rating.
- M6 front terminals at 90 in-lbs - threaded copper-alloy inserts, serviced from the aisle.
- 800 A maximum discharge - with 6.5 milliohms impedance at 60 Hz.
- Two-year storage rating - up to 24 months at 77°F before a freshening charge is required.
Technical Specifications
| C&D TEL12-105FHTG Specifications | |
|---|---|
| Part Number | TEL12-105FHTG (also searched as TEL12 105FHTG, C&D 105FHTG) |
| Battery Type | VRLA-AGM, MSE pure lead, front access, high-temperature telecom standby |
| Nominal Voltage | 12V |
| Capacity, 8-hour rate | 101 Ah to 1.75 VPC at 77°F |
| IEC Capacity, 10-hour rate | 98 Ah to 1.80 VPC at 68°F |
| Maximum Discharge Current | 800 A |
| Impedance | 0.0065 ohm at 60 Hz |
| Terminal Type | Threaded copper alloy insert, M6 bolt at 90 in-lbs (10.2 N-m) |
| Gas Management | TFA gas collection system (C&D datasheet designation for G-suffix models) |
| Length | 16.2 inches (412 mm) |
| Width | 4.2 inches (106 mm) |
| Height | 11.4 inches (289 mm) |
| Weight | 72 lbs (32.8 kg) |
| Operating Temperature | Discharge -40°F to +160°F; charge -10°F to +140°F |
| Float Charging Voltage | 13.65 VDC ±0.15 per 12V unit |
| Design Life | 12+ years (C&D, TEL-HT datasheet REV 04/03/24) |
| Warranty | 6 years (C&D) |
Where This Battery Is Used
- Cell sites and outdoor cabinets - the 100 Ah class where summer heat rules out standard VRLA.
- 19-inch and 23-inch relay racks - the short case slides where longer TEL-HT models will not.
- Enclosures with gas management requirements - installs that call for collected venting at the terminal face.
Ordering and Freight
Frequently Asked Questions
What does the G at the end of the part number mean?
It marks the TFA gas collection system, the hardware C&D flags on the TEL-HT datasheet for this model and the 170FHTG. Instead of venting diffusely, the battery routes gas through a collection path at the front-access terminals, which some enclosure designs and site specifications require. If your spec is silent on gas collection, the hardware is simply built in on this model and stays out of the way.
Can this replace my TEL12-105FNSG?
Same brand, same 100 Ah class, different construction and case. The FHTG brings pure lead grids, the extended temperature window and the 12+ year design life; the tray, however, decides. Send your shelf dimensions and the label of the unit coming out with the quote request, and the specialist confirms fit and hardware in writing before you commit either way.
Does a 101 Ah battery need an 800 A discharge rating?
Rarely at full stretch, by design. The 800 A ceiling keeps the battery clear of becoming the limit during inrush, fault clearing or a hard transfer, and a standby battery does its best work running far below its maximum rating. Reserve time still comes from the amp-hour figures, so size the string from the 8-hour rating.
Send the quantity, your delivery ZIP and your requested-by date. A specialist confirms availability, the warranty term, volume pricing and freight in writing, with no obligation to buy.