C&D TEL12-180F TEL Front Access Series Battery

$669.95
SKU: TEL12-180F
Availability: Request Quote For Availability
Minimum Purchase: 4 units
Shipping: Free shipping on orders $75 and up
Voltage: 12
Capacity: 181 AH
Chemistry: AGM
Features: TEL Long Duration Series
Terminal: Front Terminal
C&D TEL12-180F TEL Front Access Series Battery

C&D TEL12-180F TEL Front Access Series Battery

$669.95
Adding to cart… The item has been added

C&D TEL12-180F Battery - 12V 181Ah Front Access Telecom AGM

The TEL12-180F sits near the top of C&D's TEL Long Duration range: a 12V front-access monobloc rated 181 Ah at the 8-hour rate to 1.75 volts per cell, with 174 Ah at the 10-hour rate. Larger monoblocs mean fewer parallel strings for the same reserve, and fewer intercell connections across the plant. The front-access build keeps every one of them serviceable from the aisle. This is the class of battery that holds a full central office plant through a long outage rather than a short blip.

Warranty

C&D's warranty term for this model is confirmed in writing with your quote. Design life is a separate figure: the TEL series carries C&D's Telcordia-certified life exceeding 10 years.

Big Reserve, Fewer Joints

181 Ah at the 8-hour rate
Among C&D's 12V TEL Long Duration models, only the TEL 12-210 builds (202 Ah) rate higher. Sized for strings that must carry the plant through hours, not minutes.
1/4-20 threaded terminals
Bolted lug connections at 110 in-lbs, torqued and read from the front of the case.
3.7 milliohm internal resistance
With a 4,500 A short-circuit figure, the fault characteristics your protection engineer sizes breakers against.
  • Sealed AGM VRLA - non-spillable long-duration design, nothing to water.
  • TEL series certification set - SR-4228, UL 1989, UL 1778, UL 924 and the UL 94 V-0 case rating.
  • Front-access string service - readings and retorques happen without unracking a 12V monobloc of this size.

Technical Specifications

C&D TEL12-180F Specifications
Part NumberTEL12-180F (C&D's current catalog lists the model as TEL12-180Fa; also searched as TEL12 180F)
Battery TypeAGM VRLA, front access, long-duration telecom standby
Nominal Voltage12V
Capacity, 8-hour rate181 Ah to 1.75 VPC
Capacity, 10-hour rate174 Ah to 1.80 VPC
Short Circuit Current4,500 A
Internal Resistance0.0037 ohm
Terminal Type1/4-20 threaded, front access
CertificationsSR-4228, UL 1989, UL 1778, UL 924, UL 94 V-0 (TEL series)
Length22.01 inches (559 mm)
Width4.96 inches (126 mm)
Height12.60 inches (320 mm)
Weight132 lbs (60 kg)
Terminal Torque1/4-20 at 110 in-lbs (12.4 N-m)
Operating TemperatureDischarge -40°F to +160°F; charge -10°F to +140°F
Float Charging Voltage13.5 to 13.8 VDC average per 12V unit at 77°F
StorageUp to 6 months at 77°F before a freshening charge is required
Design LifeTelcordia-certified, exceeding 10 years (C&D, TEL series)
WarrantyConfirmed in writing with your quote (C&D)

Where This Battery Is Used

  • Central office plants - the -48V reserve where fewer, larger monoblocs mean fewer parallel strings.
  • Aggregation and headend sites - long-duration holdover for the equipment a region depends on.
  • Standby plants with long generator starts - sites where the battery bridges more than a transfer switch click.

Ordering and Freight

At 132 lbs per unit these ship freight pre-paid by LTL to commercial addresses; a residential or limited-access delivery adds $100, which is the liftgate and access charge the carrier bills us. A specialist returns a written quote with volume pricing in 24 to 48 hours.

Frequently Asked Questions

Is TEL12-180F the same battery as TEL12-180Fa?

C&D's current published catalog lists the model as TEL12-180Fa, and the 181 Ah rating class is the same. If your records or your existing string say 180F, send the label photo with your quote request and the specialist confirms the exact build in writing before anything ships.

What does the 4,500 A short-circuit figure mean for my install?

It is a fault characteristic, separate from any usable rating. That number tells your protection engineer what a bolted fault across the terminals can deliver, which sizes the overcurrent protection and the cable. Reserve time still comes from the amp-hour ratings, so size the string from the 8-hour figure and the load, and leave the 4,500 A to the breaker calculation.

What connects to a 1/4-20 terminal?

A bolted cable lug, torqued to 110 in-lbs (12.4 N-m). Terminal hardware varies across the TEL line, and the same-size TEL 12-210F and 210FG use M6, so check the hardware on the units coming out before you order lugs. Confirm lug sizing with the quote if you are replacing hardware along with the batteries.

How much charger ripple does the TEL line tolerate?

C&D recommends holding ripple voltage to 0.5% RMS or 1.5% peak-to-peak of the float voltage, and caps ripple current at C/20 amps RMS, which is 5 A RMS per 100 Ah.

Hot site? The same class in pure leadThe TEL12-190FHT carries 199 Ah with C&D's high-temperature MSE construction.
Get the TEL12-180F priced for your plant

Send the quantity, your delivery ZIP and your requested-by date. A specialist confirms availability, the warranty term, volume pricing and freight in writing, with no obligation to buy.

Call 1-877-775-4381  ·  battery specialists, not a call center