Free Shipping
Orders $75 & Up
-
30-day Money Back
Guarantee*
-
100% Secure Online Shopping
SSL - Verified Merchant
Power Storage 12GX210F Pure Lead Front Access Telecom Battery
Power Storage 12GX210F Pure Lead Front Access Telecom Battery
Power Storage Solutions 12GX210F Battery - 12V 210 Ah Pure Lead Front Access AGM
Warranty
The Longest Reserve in the GX Line
- Float 2.27 volts per cell - plus or minus 0.02 V, compensated at -3 mV per cell per degree C, with equalization at 2.35 to 2.40 V per cell.
- CE and UL certified, IEC 60896 - the stationary VRLA standard Power Storage Solutions publishes against the whole GX range.
- Discharge rated to 149°F - with the nominal operating range named as 77 ±5°F (25 ±3°C) and charging permitted from -4°F to 129°F.
- Non-spillable under DOT 49 CFR 173.159(d) - the classification that keeps a 133 lb block moving as ordinary non-hazardous freight.
- ISO 9001, ISO 14001, ISO 45001 and OHSAS 18001 - the manufacturing certifications behind the series, the paperwork a procurement file usually asks for.
Technical Specifications
| Power Storage Solutions 12GX210F Specifications | |
|---|---|
| Part Number | 12GX210F (also searched as 12GX 210F, 12gx210f battery, pwrss 12gx210f; sold under the Power Storage Solutions brand) |
| Series | Telecom GX, pure lead high rate, front access |
| Battery Type | AGM, valve regulated lead acid (VRLA), pure lead |
| Nominal Voltage | 12V (6 cells per unit) |
| Nominal Capacity | 210 Ah at the 8-hour rate to 1.75 VPC at 77°F (25°C) |
| Nominal Rate | 725 watts per cell at the 15-minute rate to 1.67 VPC at 77°F |
| Constant Current to 1.75 VPC | 427.4 A at 10 min, 354.2 at 15 min, 233.0 at 30 min, 143.0 at 1 hr, 60.6 at 3 hr, 26.2 at 8 hr, 21.3 at 10 hr, 11.6 at 20 hr |
| Constant Current to 1.85 VPC | 353.9 A at 10 min, 298.4 at 15 min, 206.5 at 30 min, 129.2 at 1 hr, 57.3 at 3 hr, 24.8 at 8 hr, 20.3 at 10 hr, 11.1 at 20 hr |
| Constant Current to 1.67 VPC | 479.6 A at 10 min, 384.8 at 15 min, 246.0 at 30 min, 149.4 at 1 hr, 62.7 at 3 hr, 26.5 at 8 hr, 21.7 at 10 hr, 11.8 at 20 hr |
| Constant Power to 1.75 VPC | 799.5 W/cell at 10 min, 676.0 at 15 min, 462.3 at 30 min, 279.8 at 1 hr, 120.3 at 3 hr, 51.5 at 8 hr, 23.3 at 20 hr |
| Constant Power to 1.67 VPC | 864.2 W/cell at 10 min, 725.0 at 15 min, 488.0 at 30 min, 289.3 at 1 hr, 123.5 at 3 hr, 53.0 at 8 hr, 23.5 at 20 hr |
| Short Circuit Current | 4,200 A |
| Internal Resistance | Approximately 2.9 milliohms, fully charged |
| Ohmic Reference, New Unit | 2.81 milliohms (HIOKI 3554), 3.15 milliohms (Biddle BITE 3), 1,732 siemens (Midtronics PBT-200); reference values, initial readings vary ±25 percent |
| Terminal Type | M8, with M6 optional, front access |
| Length | 22.0 inches (559 mm) |
| Width | 4.92 inches (125 mm) |
| Height | 12.9 inches |
| Weight | 133.4 lbs (60.5 kg) |
| Float Charging Voltage | 2.27 V per cell ±0.02 V (-3 mV per cell per °C) |
| Equalization Charging Voltage | 2.35 to 2.40 V per cell (-4 mV per cell per °C) |
| Maximum Charge Current | 0.3C |
| Operating Temperature | Charge -4°F to 129°F (-20°C to 54°C); discharge -40°F to 149°F; storage -4°F to 122°F (-20°C to 50°C); nominal 77 ±5°F (25 ±3°C) |
| Container Material | ABS-FR (UL94 V-0) |
| Standards | CE and UL certified; IEC 60896; manufactured under ISO 9001, ISO 14001, ISO 45001 and OHSAS 18001 |
| Design Life | 20 years (Power Storage Solutions) |
| Warranty | 5 years full replacement at 25°C (77°F) (PWRSS GX limited warranty) |
| Minimum Order | 4 units |
Where This Battery Is Used
- Long-reserve telecom plant - sites where the standard calls for eight hours at the full plant load rather than a generator bridge.
- Hardened and remote sites - locations a crew cannot reach quickly, where the reserve has to outlast the drive time.
- Capacity upgrades in an existing cabinet - adding reserve on the same 22.0 by 4.92 inch shelf cut the previous string used.
Ordering and Freight
Frequently Asked Questions
How long will a 12GX210F carry a 25 amp load?
Past eight hours to 1.75 volts per cell at 77°F, where the published figure is 26.2 amps. At ten hours the block gives 21.3 amps, so a steady 25 amp draw lands between those two columns. Raise the end point to 1.85 and the eight-hour figure falls to 24.8 amps, which puts the same load just inside eight hours. The disconnect setting decides which of those answers applies to your site.
Why are there two different resistance figures for the 12GX210F?
Because they are measured differently and used differently. The specification sheet gives approximately 2.9 milliohms internal resistance for a fully charged block. The PWRSS ohmic readings guide gives instrument-specific reference values for a new block: 2.81 milliohms on a HIOKI 3554, 3.15 on a Biddle BITE 3, 1,732 siemens on a Midtronics PBT-200, with initial readings varying up to 25 percent. Record your baseline with the instrument you will keep using, and compare later readings only against that same method.
Does the 12GX210F need a deeper shelf than the smaller GX blocks?
Deeper than the 100F, the same as the 190F. The 210F is 22.0 inches deep and 4.92 wide against the 100F's 16.0 by 4.25, and it stands 12.9 inches tall against 11.3. Against the 190F the footprint is identical and the difference is 0.3 inches of height and 6.4 lbs. Measure front to back first on any cabinet originally built for a 100 Ah class block.
Can a 12GX210F go into a string of 12GX190F blocks?
Not as a partial replacement. A series string discharges through every block equally, so the capacity available is set by the smallest unit in it, and mixing a 210 Ah block into a 190 Ah string buys nothing while complicating the ohmic baseline. Power Storage Solutions publishes no mixed-capacity guidance either way. Replace a string as a set and keep the capacities matched; if the target is more reserve, move the whole string to the 210F.
Send the quantity, your delivery ZIP and your requested-by date. A specialist confirms availability, the warranty term, volume pricing and freight in writing, with no obligation to buy.
Call 1-877-775-4381 · battery specialists, not a call centerWARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov (State of California only).