Free Shipping
Orders $75 & Up
-
30-day Money Back
Guarantee*
-
100% Secure Online Shopping
SSL - Verified Merchant
Deka Unigy II Spacesaver Battery Module - 24AVR95-33 (48V Config)
Deka Unigy II Spacesaver Battery Module - 24AVR95-33 (48V Config)
Deka Unigy II 24AVR95-33 Spacesaver System - 48V, 1,520 Ah 2V Cells
Warranty
Why the AVR95 Cell
- Interlock module, front bolting only - the patented Interlock design eliminates rear bolting, and the front shield assembles without tools.
- Seismic certification - one-piece base Interlock modules meet UBC 97 Zone 4 top-of-building requirements, certified to eight modules high.
- Microcat vent standard on the 95 - the catalyst that improves high-temperature performance is standard on the AVR95 and AVR125 cells.
- Standards named by East Penn - Unigy II products are designed to meet IEC 60896-21/22, BS 6290 and SR-4228; UL recognized component.
- Two-way post and standard 1CU connectors - the connector package supports discharge rates down to the two-hour rate to 1.75 VPC; higher-rate packages are available.
- Top or side termination - available as a standard feature at no additional cost per the flyer; side termination adds 3 inches per side to system length.
Technical Specifications
| Deka Unigy II 24AVR95-33 (48V) System Specifications | |
|---|---|
| Part Number | 24AVR95-33, 48V configuration (also searched as 24AVR95 deka unigy, AVR95-33, deka unigy ii spacesaver) |
| System Voltage | 48V nominal, 24 cells in series |
| Cell | AVR95-33, 2V, 33 plates per cell, AGM VRLA |
| Capacity, 8-hour rate | 1,520 Ah per cell to 1.75 VPC at 77°F (East Penn Form 0975) |
| Capacity, 25-hour rate | 1,807 Ah per cell (East Penn Unigy II discharge tables) |
| Capacity, 100-hour rate | 2,151 Ah per cell (East Penn Unigy II discharge tables) |
| Arrangement | Single stack, 3 wide by 8 high, Interlock modules |
| System Footprint | 39.90 inches long by 27.88 inches deep (our 48V configuration record; height depends on base and termination options and is confirmed on the quote drawing) |
| System Weight | Approximately 6,329 lbs, cells and modules (our configuration record; excludes base and hardware) |
| Positive Grid | 99.99% pure lead, IPF-formed plates |
| Posts | Lead-plated solid copper, two-way post design, Epox-Z post seal |
| Separator | Hovosorb II glass mat |
| Vent | Microcat catalyst vent |
| Container | Flame-retardant polypropylene, UL 94 V-0, LOI 28% or greater |
| Seismic | UBC 97 Zone 4, Interlock one-piece base, certified to 8 modules high |
| Standards | IEC 60896-21/22, BS 6290, SR-4228 (designed to meet); UL recognized component |
| Float Voltage | 2.25 VPC nominal; set per the Unigy II Interlock installation and operation manual |
| Design Life | 20 years in float service at 77°F (East Penn, AVR95 cell) |
| Warranty | 3 years full replacement (East Penn, Unigy II, Form 1865) |
Where This System Is Used
- 48V central office and hub-site reserve - long-duration telecom plant sized in ampere-hours over eight hours or more.
- Switchgear and substation control - the applications East Penn names on the flyer alongside telecommunications and UPS.
- Sites where floor space is the constraint - a vertical stack in place of a rack of monobloc batteries.
Ordering and Freight
Frequently Asked Questions
Is the 24AVR95-33 sold as one part or as twenty-four cells?
It is quoted as a configured system: twenty-four AVR95-33 cells, the Interlock modules that hold them, the base, the connector package and the front shields. The part number on this page is our configuration designation for the 48V, eight-high arrangement. The same cell is sold in 24V and other configurations, so if your plant is not 48V, say so and a specialist quotes the arrangement you need.
How is the 1,520 Ah figure rated?
At the 8-hour rate to 1.75 volts per cell, on East Penn's Spacesaver flyer, Form 0975. That is the telecom reserve basis. The 25-hour and 100-hour figures in the table come from East Penn's Unigy II discharge tables and apply to lower loads over longer reserves; use the column that matches the reserve time your plant is designed to.
What does Zone 4 certification mean for this stack?
The Interlock module with its one-piece base is certified to UBC 97 Zone 4 top-of-building requirements when stacked up to eight modules high, per East Penn's flyer. This 48V configuration is eight high, so it sits inside that certification. If your site falls under a different seismic code, send the requirement with the quote request and a specialist confirms the documentation East Penn can supply.
Can the system be installed and commissioned by High-Tech Battery Solutions?
Yes. For a system of this size we offer installation and removal of the outgoing string with recycling of the spent cells. Ask for it with your quote and the installation is priced alongside the battery.
Send the site address, clearances, termination preference and your requested-by date. A specialist confirms availability, the warranty term, pricing, freight and the system drawing in writing, with no obligation to buy.
Call 1-877-775-4381 · battery specialists, not a call centerWARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov (State of California only).