C&D TEL12-115FN Battery - 12V Front Access Telecom AGM
Warranty
The Long-Duration Workhorse
- Standard AGM VRLA construction - sealed and non-spillable, no watering.
- SR-4228 compliant, UL 1989, UL 1778, UL 924 and UL 94 V-0 - the certification set C&D publishes for the TEL series.
- Non-hazardous for transport - not restricted for air, surface or water freight per IATA/ICAO Special Provision A67, DOT-CFR and IMDG exception 238.
Technical Specifications
| C&D TEL12-115FN Specifications | |
|---|---|
| Part Number | TEL12-115FN (also searched as TEL12 115FN, C&D TEL12-115) |
| Battery Type | AGM VRLA, front access, long-duration telecom standby |
| Nominal Voltage | 12V |
| Capacity, 8-hour rate | 108 Ah to 1.75 VPC |
| Capacity, 10-hour rate | 106 Ah to 1.80 VPC |
| Short Circuit Current | 4,000 A |
| Internal Resistance | 0.0030 ohm |
| Terminal Type | M6 threaded, front access |
| Certifications | SR-4228, UL 1989, UL 1778, UL 924, UL 94 V-0 (TEL series) |
| Length | 20.12 inches (511 mm) |
| Width | 4.33 inches (110 mm) |
| Height | 9.25 inches (235 mm) |
| Weight | 73 lbs (33 kg) |
| Terminal Torque | M6 at 107 in-lbs (12 N-m) |
| Operating Temperature | Discharge -40°F to +160°F; charge -10°F to +140°F |
| Float Charging Voltage | 13.5 to 13.8 VDC average per 12V unit at 77°F |
| Storage | Up to 6 months at 77°F before a freshening charge is required |
| Design Life | Telcordia-certified, exceeding 10 years (C&D, TEL series) |
| Warranty | Confirmed in writing with your quote (C&D) |
Where This Battery Is Used
- Central office -48V strings - the reserve behind the rectifiers, sized in amp hours over hours.
- Remote terminals and huts - conditioned enclosures where the standard TEL build is the economical fit.
- Broadband and network powering - long-duration holdover for outside-plant electronics.
Ordering and Freight
Frequently Asked Questions
What does a Telcordia-certified life claim?
C&D states the TEL series is Telcordia tested and qualified to meet all SR-4228 requirements, and the life it publishes for the line, exceeding 10 years, carries that certification. Real service life still depends on temperature and float discipline at your site.
Do I need the high-temperature version instead?
Only if the environment says so. In a conditioned central office or a cabinet that stays near 77°F, the standard TEL build carries the duty at a lower cost basis, and buying pure lead headroom the site never uses helps nobody. Where the enclosure bakes in summer or the site skips cooling to save power, the TEL-HT line exists for exactly that, and we will tell you plainly which side of the line your site sits on.
What does sealed VRLA mean for the equipment room?
The electrolyte is held in the glass mat, so there is nothing to spill and nothing to top up. C&D rates gas recombination at 99% plus, fits a flame-arresting one-way pressure-relief vent and uses a UL 94 V-0 case. Its install note calls for at least 0.5 inch (12.5 mm) between units for free-air ventilation, and your install code has the final word.
How long can these sit before installation?
C&D allows up to 6 months at 77°F before a freshening charge is required. Time the delivery to the install date so the string is not waiting on a shelf.
Send the quantity, your delivery ZIP and your requested-by date. A specialist confirms availability, the warranty term, volume pricing and freight in writing, with no obligation to buy.