Deka Unigy HR4000 Battery - 12V 420 WPC High Rate UPS AGM
Warranty
The Rating Between 370 and 475
- VRLA with glass mat separators - puncture-resistant micro-porous mat, heat-sealed case and cover, epoxy-sealed posts, self-sealing flame-arresting valves, all 100 percent factory tested.
- UL 1973 certification for energy storage - with UL recognition requirements and IEEE recommended practices met in the construction.
- Reinforced polypropylene case - flame-retardant to UL 94 V-0 with a limiting oxygen index above 28 percent, built against bulging under high-rate discharge.
- Float voltage 13.50V per battery - plus or minus 0.5 percent at 77°F, a 13.42V to 13.57V window.
- Factory acceptance testing offered - East Penn's flyer lists an optional factory discharge at the 10-minute rate to 1.67 VPC with a formal report, priced on request with the string.
Technical Specifications
| Deka Unigy HR4000 Specifications | |
|---|---|
| Part Number | HR4000 (also searched as HR 4000, deka hr4000, deka unigy hr4000, hr4000 battery) |
| Battery Type | AGM VRLA with IPF plate technology, high rate, top terminal, UPS standby |
| Nominal Voltage | 12V |
| Rating | 420 watts per cell at the 15-minute rate to 1.67 VPC at 77°F; watt-rated, no amp-hour rating is published |
| Constant Power to 1.67 VPC | 1,227 W/cell at 1 min, 780 at 5 min, 541 at 10 min, 420 at 15 min, 344 at 20 min, 254 at 30 min, 143 at 60 min |
| Constant Power to 1.75 VPC | 1,027 W/cell at 1 min, 705 at 5 min, 404 at 15 min, 140 at 60 min |
| Positive Plate | Greater than 98% pure lead, tin-calcium alloy |
| Negative Plate | Pure lead, calcium alloy |
| Terminal Type | Top access, 1/4-20 threaded insert, epoxy-sealed posts |
| Length | 12.93 inches (328.4 mm) |
| Width | 6.84 inches (173.7 mm) |
| Height | 8.70 inches (221 mm) |
| Weight | 81 lbs (37 kg) |
| Float Charging Voltage | 13.50V per battery ±0.5% at 77°F (range 13.42V to 13.57V) |
| Case Material | Flame-retardant polypropylene, UL 94 V-0, >28% limiting oxygen index |
| Valves | Low positive pressure, self-sealing, flame arrestor |
| Standards | UL 1973; UL recognition; IEEE recommended practices |
| Design Life | 10 years in float applications at 77°F (East Penn) |
| Warranty | 3 years (East Penn, High Rate top terminal tier, Form 0986) |
| Minimum Order | 4 units |
Where This Battery Is Used
- Three-phase UPS strings - 32 to 40 blocks in series where the sizing table lands between a 370 and a 475 watt block.
- Computer rooms and network cores - ride-through to generator transfer on a top-post tray under 9 inches tall.
- Switchgear and breaker control - trip and close power on float, using the 1,227 watt 1-minute rate.
Ordering and Freight
Frequently Asked Questions
Is the HR4000 a 400 watt battery?
East Penn rates it at 420 watts per cell at the 15-minute rate to 1.67 volts per cell at 77°F on Form 2010. The 4000 is the model designation. A UPS sizing table built on 400 watts per cell will under-count the string slightly; use 420 and the published columns for other runtimes.
Where does the HR4000 sit against the HR3500 and the 31HR5000?
In the middle, on rating and on size. The HR3500 gives 370 watts per cell from a 12.01 by 6.56 by 8.24 inch case at 71.5 lbs; the HR4000 gives 420 from 12.93 by 6.84 by 8.70 inches at 81 lbs; the 31HR5000 gives 475 from 13.46 by 6.84 by 11.21 inches at 97 lbs. The HR4000 is the largest of the three that stays under 9 inches tall, which is often the deciding measurement in a UPS battery cabinet.
Does the HR4000 share a footprint with any Deka telecom block?
The 12AVR100 in the Unigy I line is 12.93 by 6.84 inches, the same length and width, at 9.33 inches tall against the HR4000's 8.70. They are different batteries for different jobs: the 12AVR100 is amp-hour rated for eight-hour reserve, the HR4000 is watt-rated for fifteen-minute ride-through. The shared footprint means a tray cut for one physically takes the other, but the sizing basis does not transfer.
What does the HR4000 deliver at a 30-minute runtime?
254 watts per cell to 1.67 VPC, or 249 to 1.75 VPC, per East Penn's table. That is 1,524 watts per block for half an hour, so a 40-block string carries roughly 61 kW for 30 minutes at 77°F. At the 60-minute column the figure is 143 watts per cell. Send the UPS load and the runtime you need and a specialist works the string count from the published row rather than from the 15-minute headline.
Send the quantity, your delivery ZIP and your requested-by date. A specialist confirms availability, the warranty term, volume pricing and freight in writing, with no obligation to buy.
Call 1-877-775-4381 · battery specialists, not a call centerWARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov (State of California only).