Leoch LPL12-75 Battery - 12V 75AH AGM Deep Cycle VRLA
Leoch LPL12-75 Battery - 12V 75AH AGM Deep Cycle VRLA
Leoch LPL12-75 Battery - 12V 75Ah Long Life Standby AGM
Warranty
Long-Life Standby Construction
- T6 threaded insert - a copper alloy terminal sized for M6 hardware, as specified on the current sheet.
- 260 x 168 mm footprint - a 10.2 x 6.61 inch case with a total height of 8.43 inches.
- 50.0 lb published weight - the current Leoch value is 22.7 kg, not the older 23 kg listing figure.
- Sealed AGM construction - a valve-regulated battery that requires no watering during service.
- Published discharge range - -15°C to 50°C (5°F to 122°F), with application conditions confirmed during quoting.
Technical Specifications
| Leoch LPL12-75 Specifications | |
|---|---|
| Part Number | LPL12-75 (also written LPL12 75, LPL 12-75 and LPL1275) |
| Series | Leoch LPL long life standby |
| Battery Type | Absorbent glass mat (AGM), valve regulated lead acid (VRLA) |
| Nominal Voltage | 12V |
| Nominal Capacity | 75Ah at the 10-hour rate to 1.80 VPC at 25°C |
| Terminal Type | T6 threaded insert for M6 bolt |
| Length | 260 mm (10.2 inches) |
| Width | 168 mm (6.61 inches) |
| Container Height | 208 mm (8.19 inches) |
| Total Height | 214 mm (8.43 inches) |
| Weight | 22.7 kg (50.0 lbs) |
| Short-Circuit Current | 1725A |
| Internal Resistance | Approximately 7.2 milliohms, fully charged, at 25°C |
| Maximum Charge Current | 0.3C at 25°C |
| Float Charge Voltage | 2.25 to 2.30 V per cell at 25°C |
| Equalization Charge Voltage | 2.35 to 2.40 V per cell at 25°C |
| Operating Temperature | Discharge -15°C to 50°C; charge -20°C to 40°C; storage -15°C to 40°C |
| Container Material | ABS, UL 94 HB standard; UL 94 V-0 optional |
| Standards | IEC 60896, EU Battery Directive, UL and CE |
| Design Life | 12 years at 25°C on float service (Leoch) |
Applications
- UPS and emergency power - standby strings for uninterruptible power supplies, emergency lighting and EPS systems.
- Signals and controls - railway and aircraft signaling, electronics and protected control circuits.
- Station and marine power - documented DC backup where case dimensions and terminal hardware have to match the enclosure.
- Security and communications - alarm systems, network equipment and communications power held on continuous float.
Ordering and Freight
Frequently Asked Questions
Is the LPL12-75 a deep-cycle battery?
The LPL12-75 is a long-life standby battery. Leoch lists UPS, emergency lighting, signaling, station power, security and communications applications. A project that cycles the battery every day should be checked against a cycle-rated product instead of being selected from voltage and amp-hour capacity alone.
Does the LPL12-75 use a T6 or T13 terminal?
The current Leoch datasheet specifies a T6 copper alloy threaded insert for an M6 bolt. The earlier T13 description does not match the current sheet. Confirm the existing connector and lug dimensions before ordering a replacement.
What is the correct LPL12-75 weight?
Leoch publishes 22.7 kg, or 50.0 lbs. Battery weights can vary slightly in production, but 50.0 lbs is the current catalog value used for this page.
Can the LPL12-75 replace another 12V 75Ah battery?
Voltage and capacity are only the starting point. The 260 x 168 x 214 mm total case size, T6 terminal, M6 hardware and the equipment's discharge requirement all have to match. Send the existing part number and installation details with the quote request for a fit check.
Send the existing part number, quantity, enclosure dimensions and requested-by date. A specialist verifies the case and terminal fit, then returns the product, lead time and freight details in one written quote.
Call 1-877-775-4381 · battery specialists, not a call centerWARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov (State of California only).